FILL PIPE 

 
If the Fill pipe is used for the insertion of a gauge stick 
to determine the amount of fuel in the tank, it is 
important the pipe be in a straight vertical position.  
The top of the pipe should be protected by a fill box or 
spill containment box to prevent frozen ground from 
pulling the tank flange loose from the tank. 
 
 
 

 
 
 
 
 
 

MUST DO

 INSTALLATION NOTES: 

 
1. Each dispenser must be earth grounded using a dedicated 12-gauge or larger green stranded ground 

wire to each pedestal.  The ground must be 1 ohm (or less) resistance to earth ground.  Terminate this 
wire at the terminal block ground lug.  All 12-gauge ground wires from each unit are terminated at the 
main electrical service panel ground.  DO NOT USE WIRE NUTS FOR GROUND CONNECTIONS.  
USE ONLY COMPRESSION CONNECTORS. 

 
2. For maximum electronic performance and system reliability, leave the dispenser “ON” 24 hours a day.  

To prevent product theft during closing hours, turn off pump motor power.  To give the appearance that 
the dispenser is shut off, activate the display blanking switch. 

 
3.  DO NOT USE ONE CIRCUIT BREAKER to supply pump motor power and dispenser electronic power.  

Separate circuits are required. 

 
4. For remote dispensers the RE/MOV filters must be installed per wiring diagram for proper operation 

(NOTE: 3 per submerged relay). 

 
5. Check with Federal, State and Local Codes for conduit use in your area.  (Rigid metal conduit is 

recommended). 

 
6.  Use only stranded wire with listed gas and oil resistant insulation.  Do not use wire smaller than listed on 

the wiring diagrams. 

 
7.  DO NOT USE WIRE NUTS ON DATA LINES.  DO NOT SPLICE DATA WIRES. 
 

8.  Anchor the dispenser to the island with four anchor bolts through the base frame.

   

WHEN ANCHORING 

THE DISPENSER, always level the dispenser with shims before bolting to the island. DO NOT shim just 
the middle of the dispenser and bolt down. 

 
9.  The 9-Volt battery found in the Electronic Compartment MUST be placed in the Power Board.  If there 

are more Power Boards in the dispenser, there will be a 9-Volt battery for each Power Board in the 
Electronic Compartment.  These MUST be inserted in each Power Board.

 

 

10.  All dispenser wiring must be 60” higher than the base of the dispenser. 

 

11.  MUST install Potting Compound to Electrical Wiring through the factory conduit. 
 
12.  MUST route Field Wiring.  Refer to Figure 12 on page 23 for installation.  

VENT PIPE 

 
The tank must be vented in accordance with the rules 
of the National Board of Fire Underwriters.  It is 
important that the vent line slope upward from the 
tank to avoid traps or pockets.  The line should be 
equipped with swing joints to prevent damage due to 
settling or freezing.  The top of the vent lines should 
be at least 10 feet above the ground and at least 5 
feet away from chimneys, windows or other openings.  
Installation must be in accordance with 

NFPA 30

 

NOTE: Make certain all installations conform to 

Federal, State, and Local codes for 
underground storage systems. 

 

 

Содержание Horizon 2200 Series

Страница 1: ...tion and operation of this equipment Read and understand this book before applying power Keep this book and tell all service personnel to read this book If you do not follow the instructions you can c...

Страница 2: ...o Calibrate the SB 100 Meter 28 Specification Sheets 29 Warranty Registration Card 30 Bennett Warranty Inside Back Cover NOTICE This equipment generates and uses radio frequency energy If not installe...

Страница 3: ...mpletely assembled WARNING When anchoring the dispenser always level the dispenser with shims before bolting to the island DO NOT shim just the middle of the dispenser and bolt down CAUTION Do not dri...

Страница 4: ...dispensers shown in this book can be operated in the Stand Alone mode no control console The 2200 Series is available with 1 or 2 Products Self contained or Remote dispenser It is also available in a...

Страница 5: ...or self contained dispensers the horizontal section of pipe from the underground storage tank should be at least 18 inches below the surface at its highest point If not extreme temperatures will conve...

Страница 6: ...cal fire regulations 2 Use new 1 1 2 or larger EPA approved pipe 3 Static lift on self contained units should not exceed 10 feet vertical distance between product level in the storage tank and the cen...

Страница 7: ...designed for under the pump mounting is installed for each pumping unit according to the valve manufacturer s instructions x Any additional valves suggested by the Pressure Regulating Valve manufactur...

Страница 8: ...101073 Rev B 3 99...

Страница 9: ...in your area Rigid metal conduit is recommended 6 Use only stranded wire with listed gas and oil resistant insulation Do not use wire smaller than listed on the wiring diagrams 7 DO NOT USE WIRE NUTS...

Страница 10: ...101073 Rev B 3 99 Figure 6 2200 Series Remote 6...

Страница 11: ...101073 Rev B 3 99 Figure 7 2200 Series Self Contained 7...

Страница 12: ...101073 Rev B 3 99 8 Figure 8 HOW TO TRANSPORT THE 2200 SERIES PREFERRED METHOD FOR HIGH HOSE...

Страница 13: ...101073 Rev B 3 99 9 Figure 9 PREFERRED METHOD FOR LOW HOSE...

Страница 14: ...ircuit breaker 2 Do not connect any other devices to these circuits 3 Each remote dispenser uses one 120V 50 60 Hz or 240V 50 60Hz circuit for dispenser power Put no more than four Horizon dispensers...

Страница 15: ...devices such as coils and across relay contacts When AC voltage is applied to coils they are converted to electromagnets Coils are used to operate AC devices such as solenoid dispensing valves and AC...

Страница 16: ...und follow this procedure 1 Connect a 12 gauge green stranded wire to the grounding terminal near the terminal block in the electronic head 2 Pull the wire through the rigid metal conduit and connect...

Страница 17: ...101073 Rev B 3 99 13 Figure 10A 2211 Series Remote...

Страница 18: ...101073 Rev B 3 99 14 Figure 10B 2212 Series Remote...

Страница 19: ...101073 Rev B 3 99 15 Figure 10C 2222 Series Remote...

Страница 20: ...101073 Rev B 3 99 16 Figure 10D 2224 Series Remote...

Страница 21: ...101073 Rev B 3 99 Figure 11A 2211 Series Self Contained 17...

Страница 22: ...101073 Rev B 3 99 18 Figure 11B 2212 Series Self Contained...

Страница 23: ...101073 Rev B 3 99 Figure 11C 2222 Series Self Contained 19...

Страница 24: ...101073 Rev B 3 99 Figure 11D 2224 Series Self Contained 20...

Страница 25: ...073 Rev B 3 99 FIELD WIRING CONDUIT INSTALLATION All field wiring must be routed through wire clips as shown in Figure 12 WARNING Do not leave extra wire length when routing the field wiring Figure 12...

Страница 26: ...101073 Rev B 3 99 The Customer must supply field conduit as shown in Figure 13 Figure 13 All 2200 Series 22 R R...

Страница 27: ...d wire routing clips See Figure 12 6 Shorten field wiring to appropriate length when making connection Do not leave excess wire See Figure 12 7 Attach data wires to power board in head and AC power wi...

Страница 28: ...eakers and all other circuit breakers to the dispenser Make sure the 12 gauge green ground wire is properly terminated near the GND Terminal on the power board and measures 1 ohm or less resistance to...

Страница 29: ...ose and lock the lower door panels and replace the upper door 3 Turn the circuit breaker for the system on 4 Purge the air from the system 5 Dispense a small amount of fuel from each hose to verify al...

Страница 30: ...pulling the pin and turning the dial until the next adjacent hole aligns with the same hub and reinserting the pin To calibrate the meter follow this procedure 1 Measure the actual delivery of the met...

Страница 31: ...2 Local Preset w Key Reset DES Keypad 0 None 1 DES Keypad Cash Acceptor 0 None 1 Cash Acceptor DCA 0 None 1 M ajor Oil DCA 2 Unbranded Option Pay 3 Unbranded Force Pay Vapor Recovery X None 1 Balanced...

Страница 32: ...tus of Warranty may be difficult to establish WARRANTY REGISTRATION WARRANTY REGISTRATION CARD A separate registration card must be filled out for each piece of equipment at the site including the I C...

Страница 33: ...country in which the product is installed Bennett Marketing Services can be contacted by mail facsimile telephone or e mail at the locations specified below Bennett Pump Company Marketing Services 121...

Страница 34: ...tion Manual is accurate at the date of publication The intent of this manual is to assist If further assistance is required please contact the Bennett Technical Service Department at 1 800 4 BENNET 1...

Отзывы: