Installation
Bennett HF H35 Instruction Manual
25
BATTERY (DC POWER) INSTALLATION
The 12-volt battery will be disconnected from the factory as shown in
. Prior to powering up the dispenser, the battery must be
plugged into J2 on the Power Distribution Board as shown in
Figure 2.9 - BATTERY (+ POSITIVE) DISCONNECTED
Figure 2.10 - BATTERY (+ POSITIVE) CONNECTED
INSTALLING THE WIRE SEPARATOR
A safe installation requires that a wire separator be installed on the wires as they are routed through the conduit and into the dispenser’s
electronic enclosure. The wire separator holds the wires apart to ensure that the seal off compound fully seals around each wire. Apply the
potting compound during the last step of installation. This will prevent flammable vapors from working their way into the electronic
enclosure. The wire separator is supplied in the plastic bag located inside the electronic enclosure attached to the sidewall.
c
AUTION: DATA WIRES (TWO 18-GAUGE PER FUELING POSITION) ARE DEDICATED TO A PARTICULAR FUELING POSITION. TO
PREVENT DAMAGE TO THE ELECTRONIC CIRCUIT BOARDS, DO NOT MIX THE DATA WIRES, OR CONNECT THEM TO ANY OTHER
DATA WIRES.
CAUTION: DO NOT USE WIRE NUTS OR SPLICES ON DATA WIRES. FAILURE OF THE SYSTEM WILL OCCUR
.
1.
Wrap some
Chico X
fiber around wires and push into conduit
assembly to prevent potting from running down the length of
the conduit as shown in
Note:
Use
Chico A05
potting compound for sealing fittings in hazardous locations.
2.
Using the wire separator provided. Install one wire in each
hole until all wires are separated.
3.
Push wire separator at least ¾ in. (109 cm) into conduit.
4.
Prepare potting compound according to directions.
5.
Using a funnel, pour potting into conduit, be sure to get
potting in between each wire.
6.
Let stand until firm.
Figure 2.11 - WIRING INSTALLATION
REPLACE THE SAFETY COVERS
WARNING: ALL COVERS MUST BE RETURNED TO THEIR DESIGNED LOCATIONS OR THE PUMP WILL BE UNSAFE TO OPERATE
AND THE WARRANTY ON THIS UNIT WILL BE VOIDED.
1.
Replace the power board cover if removed at the start of the wiring process and make sure that all four nuts that were removed are
replaced and properly tightened.
Note:
Perform this operation with the dispenser power off.
2.
Replace the junction box cover and make sure all nuts that were removed are replaced and properly tightened.
3.
Check that the 819 CPU cover on the back of the computer module is in place and the nuts are properly tightened.
4.
Close and lock all dispenser doors. Open inlet shut-off ball valve.
Содержание HIGH FLOW H35
Страница 12: ...Product Introduction Bennett HF H35 Instruction Manual 8 DISPENSER IDENTIFICATION NUMBER DIN...
Страница 84: ...Schematics Bennett HF H35 Instruction Manual 80 CHAPTER 8 SCHEMATICS...
Страница 85: ...Schematics Bennett HF H35 Instruction Manual 81...
Страница 86: ...Schematics Bennett HF H35 Instruction Manual 82...
Страница 87: ...Schematics Bennett HF H35 Instruction Manual 83...
Страница 88: ...Schematics Bennett HF H35 Instruction Manual 84...
Страница 89: ...Schematics Bennett HF H35 Instruction Manual 85...
Страница 90: ...Schematics Bennett HF H35 Instruction Manual 86...
Страница 91: ...Schematics Bennett HF H35 Instruction Manual 87...
Страница 92: ...Schematics Bennett HF H35 Instruction Manual 88...
Страница 93: ...Schematics Bennett HF H35 Instruction Manual 89...
Страница 94: ...Schematics Bennett HF H35 Instruction Manual 90...
Страница 95: ...Schematics Bennett HF H35 Instruction Manual 91...
Страница 96: ...Schematics Bennett HF H35 Instruction Manual 92...
Страница 97: ...Schematics Bennett HF H35 Instruction Manual 93...
Страница 98: ...Schematics Bennett HF H35 Instruction Manual 94...