7
The minimum time is obtained by rotating the trimmer completely anticlockwise.
Note: TL is read by the control unit only at end of operation. Hence, if the Trimmer position is
changed to modify the following operation it is necessary to wait for the TL of the previuous
movement to elapse, otherwise cut power off the unit to reset.
TRAC This allows to regulate the delay time after which the second gate leaf starts its closing move-
ment. The adjustment ranges from 1 sec. min. to 40 sec. max
The minimum time is obtained by turning the trimmer completely anticlockwise.
Programming of the control unit
To erase the remote control codes from memory
To erase the codes from the memory, power the control unit by keeping the PGM programming push-
button pressed. The flashing light switches on. When the flashing light switches off, the memory is
erased.
To store a new remote control code in memory
Press the PGM programming button, SCA will start to flash fast until a new remote control is received
and stored in memory. If, after pressing the button, SCA is not flashing but the flashing light for 5S
switches on, this means that memory is full and no more codes can be stored in.
Adjustment of the motor power
A faston connector is provided on the power transformer which allows to adjust the power of motors on
4 different levels. The minimum power is obtained by moving the Faston to120, by moving the Faston to
230 the power will be maximum.