Beninca CP.BISON OTI Скачать руководство пользователя страница 7

18

LOGIC (

LOG

)

MENU

FUNCTION

ON-OFF-(Default)

MEMO

TCA

Enables or disables automatic closing
On: automatic closing enabled
Off: automatic closing disabled

(OFF)

IBL

Enables or disables multi-flat function.
On: multi-flat function enabled. The step-by-step and perdestrian commands have 
no effect during the opening phase.
Off: multi-flat function disabled.

(OFF)

IBCA

During the TCA phase, the PP controls are enabled or disabled.
On: PP controls are disabled.
Off: PP controls are enabled.

(OFF)

SCL

The rapid closure is enabled or disabled. It can be activated only if TCA:ON
On: enabled rapid closure. With open gate, the photocell activation causes the 
automatic closure after 3 s. 
If the photocell is activated during the opening phase, the operation is completed 
and closure starts after 3s 
Off: disabled rapid closure.

(OFF)

PP

The operating mode of “P.P. Push button” and of the transmitter are selected.
On: Operation: OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >

(OFF)

PRE

Forewarning flashing light enabled or disabled.
On: enabled forewarning flashing light. The flashing light is activated 3 s before the 
starting of the motor.
Off: disabled forewarning flashing light.

(OFF)

HTR

The Service Man function is enabled or disabled.
On: Service Man operation. The OPEN/CLOSE push buttons should be kept 
pressed for the entire operating time.
Off: Automatic operation.

(OFF)

LTCA

During the TCA time, the blinker is enabled or disabled.
On: Enables blinker.
Off: Disables blinker.

(OFF)

ENC

The Encoder is enabled or disabled.
On: Activated Encoder.
Off: Not activated Encoder. The encoder only detects the door/gate stroke. In the 
event of maintenance operations, it is advisable to deactivate it only temporarily.

(ON)

Pho1

The PHOT 1 input is enabled or disabled in the opening phase.
On: Photocell 1 activated only in the closing phase.
Off: Photocell 1 activated in both opening and closing phases.

(OFF)

Pho2

As per PH01, but referred to PHOT 2 input.

(OFF)

Pho3

As per PH01, but referred to PHOT 3 input.

(OFF)

Pho4

As per PH01, but referred to PHOT 4 input.

(OFF)

tst1

The check on the photocell connected to PHOT1 input is activated or deactivated
Before operation, the control unit checks the switching of the photocell contact. 
If the checks are not successful, the door/gate will not move.
On: activated check on photocell.
Off: deactivated check on photocell.

(OFF)

tst2

As for TST1, but referred to PHOT2 input

(OFF)

tst3

As for TST1, but referred to PHOT3 input

(OFF)

tst4

As for TST1, but referred to PHOT$ input

(OFF)

MINV

The opening direction of the motor is selected (see Fig. 4):
On: Right side motor mount 
Off: Left side motor mount

(OFF)

CVAR

The code programmable transmitters is enabled or disabled.
On: Radio receiver enabled only for rolling-code transmitters.
Off: Receiver enabled for rolling-code and programmable code transmitters (self-
learning and Dip Switch).

(OFF)

Содержание CP.BISON OTI

Страница 1: ...L8542935 02 2019 rev 5 UNIONE NAZIONALE COSTRUTTORI AUTOMATISMI PER CANCELLI PORTE SERRANDE ED AFFINI CP BISON OTI...

Страница 2: ...SHIELD ANT ANT VOLTAGE SELECT S F4 8k2 DAS P P COM PED COVER INVERTER AUX OUT CLOSE STOP OPEN SWC Close SWO Open PHOT 1 PHOT 2 PHOT 3 PHOT 4 COM LAMP 230Vac PHOTOTEST LAMP 24Vac SCA FILTER INVERTER s...

Страница 3: ...must meet the requirements of the standards in force and outlined by CE marking ELECTRICAL SAFETY An omnipolar switch section switch with remote contact opening equal to or higher than 3mm must be pr...

Страница 4: ...3 Input Limit switch 3 NC contact It can be disconnected in the opening phase see PH03 logics 29 PHOT 4 Input Limit switch 4 NC contact It can be disconnected in the opening phase see PH04 logics 30...

Страница 5: ...inverters which are not supplied by the manufacturer for any reason whatsoever PROGRAMMING The programming of the various functions of the control unit is carried out using the LCD display on the cont...

Страница 6: ...y 0 90 0 blc Stop space is adjusted after reaching the opening and closing limit switch This value is expressed in centimetres See section How to adjust speed and braking 1 10 3 TLS It is activated wi...

Страница 7: ...rating time Off Automatic operation OFF LTCA During the TCA time the blinker is enabled or disabled On Enables blinker Off Disables blinker OFF ENC The Encoder is enabled or disabled On Activated Enco...

Страница 8: ...waiting for Push a transmitter code to be erased from memory If the code is valid it will be stored in memory and OK will be displayed If the code is not valid the Err message will be displayed RTR T...

Страница 9: ...in IMPORTANT TAKE NOTE of the protection code and KEEP IT IN A SAFE PLACE for future maintenance operations To remove the code from a protected control unit enter the programming mode with the passwo...

Страница 10: ...elf learning cannot be carried out If the stroke self learning is carried out with disabled encoder the ERR message is shown To disable the Encoder it is MANDATORY to adjust the TM parameter by subtra...

Страница 11: ...are version appears turned by 180 Normally proceed with programming DIAGNOSTICS In the event of malfunctions by pressing key or the status of all inputs limit switches control and safety can be displa...

Страница 12: ...3 2007 A1 2011 EN 60335 1 2012 A11 2014 EN 60335 2 103 2015 50581 2012 Control box 230 400Vac Name des Herstellers Adresse Codice postale e Citt Telefon E mail EG Konformit tserkl rung DOC Erkl rt da...

Отзывы: