31
RCMB423_D00241_01_M_XXEN/12.2016
6. Setting ranges, factory setting, LEDs
6.1
Parameters
Me
nu
Pa
ra
m
e
te
rs
Description
Setting
range
Fa
ct
o
ry
se
tting
AL
I2 >
Alarm value main alarm I2;
"Greater than"-comparison
30 mA…3.0 A 30 mA
I2 <
Alarm value main alarm I2;
"Less than"-comparison
I2 >
(win-
dow)
Alarm value main alarm I2;
Window-comparison (upper limit)
I1 >
Alarm value prewarning I1;
"Greater than"-comparison
50…100 %
50 %
I1 <
Alarm value prewarning I1;
"Less than"-comparison
100…200 %
150 %
I1 <
(win-
dow)
Alarm value prewarning I1;
Window-comparison (lower limit)
50…100 %
50%
Hys
Hysteresis for alarm values
10…25 %
15%
out
M
Memory function for alarm messages
off/on/con
ON
1
Position N/O contact relay 1 (11-14)
without alarm
n.c. / n.o.
n.c.
2
Position N/O contact relay 2 (21-24)
without alarm
n.c. / n.o.
n.c.
RL
Number of reload cycles
0…100
0
Содержание RCMB423EM
Страница 16: ...Function 16 RCMB423_D00241_01_M_XXEN 12 2016...
Страница 34: ...Setting ranges factory setting LEDs 34 RCMB423_D00241_01_M_XXEN 12 2016...
Страница 43: ......