Overview Modbus registers (RCMS150-01 only)
38
RCMS150_D00259_01_M_XXEN/08.2021
6.6 Control commands
Register Property
Description
Format
Setting range
Factory
setting
Comment
59000
RW
Allow register write
access
UINT16
0 = Deny
1 = Allow
0 1)
59001
RW
K1
Test
UINT16
Read
0 = No test per-
formed yet
1 = Test running
2 = Test successful
3 = Test failed
Write
1 = Start test
0
2)
59002
RW
K2
UINT16
59003
RW
K3
UINT16
59004
RW
K4
UINT16
59005
RW
K5
UINT16
59006
RW
K6
UINT16
59007
WO
K1
Fault mem-
ory reset
UINT16
1 = Perform reset
—
3)
59008
WO
K2
UINT16
—
59009
WO
K3
UINT16
—
59010
WO
K4
UINT16
—
59011
WO
K5
UINT16
—
59012
WO
K6
UINT16
—
59013
WO
K1
Load factory
settings
UINT16
1 =
Apply factory set-
tings
—
4)
59014
WO
K2
UINT16
—
59015
WO
K3
UINT16
—
59016
WO
K4
UINT16
—
59017
WO
K5
UINT16
—
59018
WO
K6
UINT16
—
59019
WO
Load channel-inde-
pendent factory
settings (without
interface)
UINT16
1 =
Apply factory set-
tings
—
5)
59020
WO
Load channel-inde-
pendent factory
settings (with inter-
face)
UINT16
1 =
Apply factory set-
tings
—
6)
59021
RW
Device signalling
UINT16
0 = off
1 = on
0 7)
59022
RW
Test alarm
UINT16 0…12
0
8)