Modbus Register Map
95
PEM330-333_D00004_01_M_XXEN/08.2015
8.11 DOx control
The DI control register are implemented as "Write-Only" registers (WO) and
are set with the function code 0x05. In order to query the current DO status,
the register
40066
has to read out.
PEM executes commands to the outputs in two steps (
ARM before EXECUT-
ING
): Before sending an open or close command to one of the outputs, it must
be activated first. This is achieved by writing 0xFF00 to the appropriate DO
register. If an "Execute" command is not received within 15 seconds, the out-
put will be deactivated again.
Each command to be executed sent to an output not being activated before,
will be ignored by the PEM333… and returned as an exception code 0x04.
Register
41007
activates/deactivates the function "
ARM before EXECUT-
ING
".
Tab. 8.18: Digital output control register
Register Property
Format
Description
60064
WO
UINT16
Activate close DO1
60065
WO
UINT16
Execute close DO1
60066
WO
UINT16
Activate open DO1
60067
WO
UINT16
Execute open DO1
60068
WO
UINT16
Activate close DO2
60069
WO
UINT16
Execute close DO2
60070
WO
UINT16
Activate open DO2
60071
WO
UINT16
Execute open DO2
60072…60127
Reserved
60128
WO
UINT16
Activate reset alarm LED and buzzer
60129
WO
UINT16
Execute reset alarm LED and buzzer