Bender LINETRAXX CTUB103 Series Скачать руководство пользователя страница 4

Index

Action

LED

6

Release the "T" button (9).

flashes 

red 

quickly

7

Calibration successful

lights 

green

Calibration not successful: repeat calibration

flashes 

red

Device view

No.

CTUB103

Note

1

Terminal  X

S1 (k)

Connection measuring current 

transformer core/NGRM…

2

S2 (l)

3

-

Not in use

4

-

5

24 V

Supply voltage 

U

S

6

GND

7

-

Not in use

8

-

9

Button T 

Offset calibration (see below)

10

Combined LED 

lights green   normal operation 

flashes red  device error; 

U

S

 is connected, no connection to CTBC.  

 

Check the connection between CTUB and CTBC, if necessary, snap on the electronic module  

 

again. If LED still flashes red: Contact Service please.

11

Potentiometer 

for adjusting the 

measuring range 

Measuring range

Scaling

5 A

5 A/50 mA

100:1

10 A

10 A/50 mA

200:1

25 A

25 A/50 mA

500:1

1

11

10

9

2 3 4

5 6 7 8

Offset-Calibration

 

i

For measuring current transformer cores with an internal diameter ≥ 120 mm, an offset calibration should 

always be carried out before the first commissioning.  Note that during the offset calibration the system is 

switched off and no current flows through the measuring current transformer. For safety reasons, offset 

calibration cannot be performed if a current > 15 mA flows through the measuring current transformer 

during offset calibration.

Index

Action

LED

1

Disconnect X plug (1…8) or interrupt US (24 V). off

2

Press and hold the "T" button (9).

off

3

Connect X plug (1…8) or switch on US (24 V).  

Continue to hold the "T" button (9) down.

lights red

4

Continue to hold the "T" button (9) down.

flashes 

red

5

Continue to hold the "T" button (9) down.

flashes 

red 

quickly

CTUB103_D00410_02_M_XXEN / 09.2022

LINETRAXX® CTUB103

Содержание LINETRAXX CTUB103 Series

Страница 1: ...Manual EN CTUB103_D00410_02_M_XXEN 09 2022 LINETRAXX CTUB103 AC DC sensitive measuring current transformer...

Страница 2: ...al safety instructions Part of the device documentation in addition to this manual is the enclosed Important safety instructions for Bender products Mounting connection and commissioning are to be car...

Страница 3: ...2 24 60 2 36 56 2 20 78 3 07 C CTUB103 CTBC120 188 7 40 225 8 86 96 3 78 120 4 72 65 2 56 96 3 78 139 5 47 D CTUB103 74 2 91 44 1 73 30 1 18 32 1 26 4 6 0 18 b c d a e d e f c b a d e f c b a g a d e...

Страница 4: ...A 50 mA 100 1 10 A 10 A 50 mA 200 1 25 A 25 A 50 mA 500 1 1 11 10 9 2 3 4 5 6 7 8 Offset Calibration i For measuring current transformer cores with an internal diameter 120 mm an offset calibration sh...

Страница 5: ...ce make sure that the installation has been de ener gised Observe the rules for working on electrical installations Observe the information on no minal voltage and supply voltage specified in the tech...

Страница 6: ...the meas uring current transformer Never route an existing protective conductor through the measuring current transformer PE L1 L2 L3 N P1 K YE P2 L GY The primary conductors may only be bent from th...

Страница 7: ...ue CTBC35 0 6 Nm CTBC60 CTBC120 1 Nm Other Operating mode continuous operation Mounting any position Degree of protection built in components DIN EN 60529 IP40 Degree of protection terminals DIN EN 60...

Страница 8: ...fo bender de www bender de All rights reserved Reprinting and duplicating only with permission of the publisher Bender GmbH Co KG PO Box 1161 35301 Gr nberg Germany Londorfer Str 65 35305 Gr nberg Ger...

Отзывы: