Data
74
CMS460-D_D00045_01_M_XXEN/07.2016
Terminating resistor .................................................................................. 120 Ω (0.25 W) connectable via DIP switch
Device address, BMS bus ............................................................................................................................ 1…90 (2)*
Cable lengths for W…, WR…, WS…, WF… series measuring current
transformers
Single wire
≥
0.75 mm
2
................................................................................................................................... 0…1 m
Single wire, twisted
≥
0.75 mm
2
................................................................................................................... 0…10 m
Shielded cable
≥
0.5 mm
2
.............................................................................................................................. 0…40 m
Recommended cable (shielded, shield connected to terminal l at one end, must not be earthed)....... J-Y(St)Y min.
.2x0.8
Switching elements
Number of changeover contacts ...........................................................................................2 x 1 changeover contacts
Operating principle .......................................................................................... N/C or N/O operation (N/O operation)*
Electrical endurance, number of cycles................................................................................................................ 10,000
Contact data acc. to IEC 60947-5-1
Utilisation category ....................................................................................... AC-13 AC-14 DC-12 DC-12 DC-12
Rated operational voltage.............................................................................230 V 230 V 24 V 110 V 220 V
Rated operational current (common alarm relay)............................................5 A 3 A 1 A 0.2 A 0.1 A
Rated operational current (alarm relay).......................................................... 2 A 0.5 A 5 A 0.2 A 0.1 A
Minimum contact rating............................................................................................................. 1 mA at AC/DC
≥
10 V
Environment/EMC
EMC............................................................................................................................................................... IEC 61326-1
Operating temperature.......................................................................................................................................... -25 °C
Climatic class acc. to IEC 60721
Stationary use (IEC 60721-3-3)......................................................... 3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2) ................................................................ 2K3 (except condensation and formation of ice)
Long-term storage (IEC 60721-3-1)................................................. 1K4 (except condensation and formation of ice)
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3)................................................................................................................................ 3M4
Transport (IEC 60721-3-2) ....................................................................................................................................... 2M2
Long-term storage (IEC 60721-3-1)........................................................................................................................ 1M3
Содержание LANTRAXX CMS460-D
Страница 6: ......
Страница 21: ...Installation and connection 21 CMS460 D_D00045_01_M_XXEN 07 2016 4 3 2 Wiring diagram ...
Страница 26: ...Installation and connection 26 CMS460 D_D00045_01_M_XXEN 07 2016 ...