Operation and configuration
43
isoLR275_D00127_00_M_XXEN/07.2018
The function of the current output is dependent on the selected
R
Sk
.
Function 0…20 mA:
R
F
= insulation fault, I = current
in mA
Function 4…20 mA:
R
F
= insulation fault, I = current
in mA
Refer to the associated characteristic curves on page 69.
For UL applications:
The analogue output as such is not a “safe alarm” indication in compliance
with UL1998. If the analogue output is intended to be used as a “safe alarm”:
– the relay output (at least K1 or K2) must additionally be used to
provide redundancy
OR
– both the relay outputs and the analogue output must be evaluated
during the cyclic self-test, in order to ensure the proper functioning
of the analogue output.
R
F
=
20 mA x R
Sk
I
- R
Sk
R
F
=
16 mA x R
Sk
- R
Sk
I
- 4 mA