Operation and setting
55
IRDH275_D00122_03_M_XXEN/05.2017
6.5.2
Adaptation to the system leakage capacitance
(Cemax: 150
μ
F)
This menu allows to adapt the ISOMETER® to the maximum system leakage
capacitance (max. 500 μF). Please note that the basic measuring time will be
increased to approximately 10 seconds when the setting is
C
e
= 500 μF. Facto-
ry setting = 150 μF.
6.5.3
Changing the measuring principle from AMP to DC
(Measure: AMP)
The DC measuring principle is only suitable for pure AC systems.
Factory setting = AMP.
6.5.4
Setting the repetition time for automatic self tests
(Autotest: 24h)
The time for the repetition of automatic self tests can either be set to 1 hour
or to 24 hours or can be deactivated.
Factory setting = 24 h
6.5.5
Setting the real-time clock (Clock) (IRDH275B)
The setting of the real-time clock is the time base for the memory and for the
automatic self test. In case of failure of the supply voltage, the real-time clock
keeps running for approximately 30 days. When the device will be switched
on after this period, a flashing "C" appears on the display and the clock has to
be set again.
6.5.6
Setting the date (Date) (IRDH275B)
As well as the time, the date is required for the memory, too. In the event of
power supply failure, the date function is not influenced for at least 30 days. If
the device is switched on again after this period, a new setting of date and
time of the real-time clock is required.
Содержание ISOMETER IRDH275
Страница 36: ...Anschluss 36 IRDH275_D00122_03_M_XXDE 05 2017 ...
Страница 38: ...Inbetriebnahme Schema dreiteilig 38 IRDH275_D00122_03_M_XXDE 05 2017 Inbetriebnahme des ISOMETER s 2 ...
Страница 40: ...Inbetriebnahme Schema dreiteilig 40 IRDH275_D00122_03_M_XXDE 05 2017 ...
Страница 91: ...91 IRDH275_D00122_03_M_XXDE 05 2017 W Werkseinstellungen 73 Z Zulassungen 79 ...
Страница 128: ...Connection 36 IRDH275_D00122_03_M_XXEN 05 2017 ...
Страница 130: ...Commissioning flow chart threepart 38 IRDH275_D00122_03_M_XXEN 05 2017 Commissioning of the ISOMETER 2 ...
Страница 132: ...Commissioning flow chart threepart 40 IRDH275_D00122_03_M_XXEN 05 2017 ...
Страница 144: ...Operation and setting 52 IRDH275_D00122_03_M_XXEN 05 2017 Diagram ISO SETUP ...
Страница 152: ...Operation and setting 60 IRDH275_D00122_03_M_XXEN 05 2017 6 6 4 Diagram COM SETUP IRDH275B ...
Страница 154: ...Operation and setting 62 IRDH275_D00122_03_M_XXEN 05 2017 6 7 2 Diagram PASSWORD ...
Страница 183: ...91 IRDH275_D00122_03_M_XXEN 04 2017 ...