![Bender ISOMETER IRDH275 Скачать руководство пользователя страница 136](http://html.mh-extra.com/html/bender/isometer-irdh275/isometer-irdh275_manual_2731635136.webp)
Operation and setting
44
IRDH275_D00122_03_M_XXEN/05.2017
Activating the TEST button starts the
ISOMETER® self test.
Pressing the RESET button resets insula-
tion fault alarms stored in the ISOMETER®.
The memory function is only available af-
ter activating the fault memory in the ISO SETUP menu or after bridging the
terminals R1/R2. Furthermore, the ISOMETER® can only be reset when the
present insulation value is 25 % higher than the set response value.
The menu system is called up by pressing the MENU key.
For controlling the menu system, the arrow keys, the ENTER key and the ESC
key are used:
Arrow up key:
Moving up in the menu, increasing a parameter
Arrow down key:
Moving down in the menu, reducing a parameter
TEST
RESET
MENU
TEST
RESET
Содержание ISOMETER IRDH275
Страница 36: ...Anschluss 36 IRDH275_D00122_03_M_XXDE 05 2017 ...
Страница 38: ...Inbetriebnahme Schema dreiteilig 38 IRDH275_D00122_03_M_XXDE 05 2017 Inbetriebnahme des ISOMETER s 2 ...
Страница 40: ...Inbetriebnahme Schema dreiteilig 40 IRDH275_D00122_03_M_XXDE 05 2017 ...
Страница 91: ...91 IRDH275_D00122_03_M_XXDE 05 2017 W Werkseinstellungen 73 Z Zulassungen 79 ...
Страница 128: ...Connection 36 IRDH275_D00122_03_M_XXEN 05 2017 ...
Страница 130: ...Commissioning flow chart threepart 38 IRDH275_D00122_03_M_XXEN 05 2017 Commissioning of the ISOMETER 2 ...
Страница 132: ...Commissioning flow chart threepart 40 IRDH275_D00122_03_M_XXEN 05 2017 ...
Страница 144: ...Operation and setting 52 IRDH275_D00122_03_M_XXEN 05 2017 Diagram ISO SETUP ...
Страница 152: ...Operation and setting 60 IRDH275_D00122_03_M_XXEN 05 2017 6 6 4 Diagram COM SETUP IRDH275B ...
Страница 154: ...Operation and setting 62 IRDH275_D00122_03_M_XXEN 05 2017 6 7 2 Diagram PASSWORD ...
Страница 183: ...91 IRDH275_D00122_03_M_XXEN 04 2017 ...