6.8 Control commands to be used in the BMS Slave mode
6.8.1 Starting and stopping EDS systems
Writing to
FTC470XMB (= output data of the Modbus RTU Master)
Table 6.71: Master request: BMS Master is intended to control the EDS system
* The value "address" consists of :
„Address“ = (BMS address x 100) + channel number
Reading from
FTC470XMB (= input data of the Modbus RTU Master)
Table 6.72: FTC reply to: BMS Master is intended to control the EDS system
Function
Devices
Word 2
Word 3
Word 4
Word 5
BMS
address
Chann
el No.
„0“
BMS
comma
nd
„0“
Data
type
Data
value
Command to BMS Master to start insulation
fault location of an EDS system
address
0
0
115
0
3
0
Command to BMS Master to stop insulation
fault location of an EDS system
„
0
0
115
0
4
0
Command to BMS Master to start insulation
fault location of an EDS system in POSITION
mode
„
1... 12
0
115
0
5
BMS
a
channel
*
No answer
Address
0
0
115
0
255
255
Acknowledgement
„
0
0
115
0
data
type
value