The FTC470XMB protocol converter
15
4.2.2
DIP switch for setting the baud rate
Valid baud rates can be set between 1200 bit/s and 57600 bit/s. The standard value for Mod-
bus RTU is 19200 bit/s.
Setting 0, all DIP switches in position OFF, is invalid and not allowed!
4.2.3
DIP switches for Modbus RTU parity
Valid parity settings are none/even/odd. The standard value for Modbus RTU is "none pari-
ty“. If Parity is none two stop bits are used, if parity is even or odd only one stop bit is used.
Setting 0 -all DIP switches in OFF position- is invalid and must not be used!
Baud rate DIP
switches
Bit/s
8
1
2
1200
0
0
1
2400
0
1
0
4800
0
1
1
9600
1
0
0
19200
1
0
1
38400
1
1
0
57600
1
1
1
Parity
DIP
switches
Parity
3
4
none
0
1
even
1
0
odd
1
1
ON
ON
ON
1
1 2 3 4 5 6 7 8
1 2 3 4
B2 B1 B0
BAUDR.
0
1
ON
ON
ON
1
1 2 3 4 5 6 7 8
1 2 3 4
PARITY
P1 P0
0
1