Operation
40
6.4
The main menu
6.4.1
Menu 1: Alarm/meas. values
EDS460-DG displays the following for each measuring channel: Alarm
status, test current I(ds), residual current I(d).
Column 1:
Channel number 1…12
Column 2:
Alarm status:
No alarm
Alarm
Column 3:
I(ds):
Currently measured test current.
Column 4:
I(d):
Currently measured residual current.
The accuracy of the displayed test current depends on the
system leakage capacitances.
The IRDH575 / PGH... test current is limited. Consequently,
the insulation fault resistance may in fact be lower than
the displayed test current suggests.
I(ds)
I(d)
1. 6mA
120mA
2.
--
<20mA
3. Channel disabled