Technical data
42
CMD420_421-DM_D00224_01_M_XXEN/08.2016
Response values CMD420-DM
Undercurrent Lo < I (Alarm 2) n = 1 .........................................................................................AC 0.1…1 A (0.3 A)*
Undercurrent Lo < I (Alarm 1) n = 1 ..................................................................................... 100…200 % (150 %)*
........................................................................................ Take a maximum nominal current of 1 A into consideration!
Overcurrent Hi > I (Alarm 2) n = 1 .................................................................................. AC 0.1…1 A (0.3 A)* (Hi)*
Overcurrent Hi > I (Alarm 1) n = 1 .................................................................................. 50…100 % (50 %)* (Hi)*
Window In > I (Alarm 2) n = 1..................................................................................................AC 0.1…1 A (0.3 A)*
Window In < I (Alarm 1) n = 1.................................................................................................. 50…100 % (50 %)*
External current transformer ...................................................................................................................................x/1 A
Transformation ratio factor n .................................................................................................................. 1…2000 (1)*
Relative uncertainty in the range 42…460 Hz...................................................................................±5 %, ±2 digits
Hysteresis ......................................................................................................................................... 3…40 % (15%)*
Measuring circuit CMD421-DM
Nominal measuring range (r.m.s. value)......................................................................................................AC 0…5 A
Overload capability, continuous ............................................................................................................................. 7.5 A
Overload capability < 5 s ............................................................................. for screw-type terminal connection 20 A
......................................................................................................................... for push-wire terminal connection 12 A
Load per measuring input ...................................................................................................................................... 3 mΩ
Rated frequency f
n
..................................................................................................................................... 42…460 Hz
Response values CMD421-DM
Undercurrent Lo < I (Alarm 2) n = 1 .........................................................................................AC 0.5…5 A (1.5 A)*
Undercurrent Lo < I (Alarm 1) n = 1 ..................................................................................... 100…200 % (150 %)*
........................................................................................ Take a maximum nominal current of 5 A into consideration!
Overcurrent Hi > I (Alarm 2) n = 1 .................................................................................. AC 0.5…5 A (1.5 A)* (Hi)*
Overcurrent Hi > I (Alarm 1) n = 1 .................................................................................. 50…100 % (50 %)* (Hi)*
Window In > I (Alarm 2) n = 1..................................................................................................AC 0.5…5 A (1.5 A)*
Window In < I (Alarm 1) n = 1.................................................................................................. 50…100 % (50 %)*
External current transformer ...................................................................................................................................x/5 A
Transformation ratio n ............................................................................................................................ 1…2000 (1)*
Relative uncertainty in the range 42…460 Hz...................................................................................±5 %, ±2 digits
Hysteresis ......................................................................................................................................... 3…40 % (15%)*