Installation, connection and commissioning
24
CMD420_421-DM_D00224_01_M_XXEN/08.2016
4.4
Factory setting
4.5
Maintenance
A functional test is recommended to be carried out at regular intervals. It is
preferable to check correct alarm indication by means of a current fault.
Also check that the terminal connections are mechanically secure.
CMD420-DM
Response value overcurrent I1 (prewarning)
Response value overcurrent I2 (alarm)
100-% value of the analogue output
CMD421-DM
Response value overcurrent I1 (prewarning)
Response value overcurrent I2 (alarm)
100-% value of the analogue output
CMD420-DM / CMD421-DM
Hysteresis:
Fault memory M:
Analogue interface type
Start-up delay:
Monitoring function:
Transformation ratio n
Password:
0.15 A (50 % of I2)
0.30 A
I > 0.30 A
0.75 A (50 % of I2)
1.50 A
I > 1.50 A
15 %
activated (on)
0…20 mA
t = 0.5 s
Overcurrent (HI)
1
0, deactivated (Off)