Power Quality
59
PEM735_D00084_02_M_XXEN/06.2020
The display shows:
For voltage swell classification, the percentages of the voltage levels u are summarised
as follows:
u ≥ 200
200 > u ≥ 160
160 > u ≥ 140
140 > u ≥ 120
120 > u >110
6.3.10
Voltage sags
Voltage sags are typically originated by faults occurring in the public network or in the
systems of network users. The nominal supply voltage
U
n
is used as reference. The volt-
age sag start threshold is equal to 90 % of the
U
n
, the hysteresis is 2 %.
The ratio between the residual voltage
U
res
and the nominal supply voltage
U
n
is dis-
played as a percentage value.
Display text
Description
t
Duration of the swells (ms)
Voltage swells u
(%)
Voltage swell level in %
Use the
and
buttons to navigate through the individual pages of
the voltage swells.
Press the "ENTER" or the "ESC" button to return to the report overview.
EN 50160 does not specify limits for these measured values.
Содержание B93100735
Страница 1: ...PEM735 PEM735_D00084_02_M_XXEN 06 2020 Power quality analyser Software version 2 00 xx Manual EN...
Страница 18: ...Device description 18 PEM735_D00084_02_M_XXEN 06 2020...
Страница 34: ...Commissioning and operation 34 PEM735_D00084_02_M_XXEN 06 2020...
Страница 66: ...Voltage 66 PEM735_D00084_02_M_XXEN 06 2020...
Страница 68: ...Current 68 PEM735_D00084_02_M_XXEN 06 2020...
Страница 72: ...Waveform 72 PEM735_D00084_02_M_XXEN 06 2020...
Страница 76: ...Harmonics 76 PEM735_D00084_02_M_XXEN 06 2020...
Страница 80: ...Metering 80 PEM735_D00084_02_M_XXEN 06 2020...
Страница 84: ...System 84 PEM735_D00084_02_M_XXEN 06 2020...
Страница 91: ...Settings 91 PEM735_D00084_02_M_XXEN 06 2020 Fig 15 6 Settings display Ethernet change settings...
Страница 98: ...Settings 98 PEM735_D00084_02_M_XXEN 06 2020...
Страница 112: ...Glossary and terms 112 PEM735_D00084_02_M_XXEN 06 2020...
Страница 115: ......