Modbus register assignment of the ISOMETER®
33
isoGEN523_D00320_04_M_XXEN/06.2018
3017
RW
Parity "Adr 2"
UINT 16
---
0 = 8N1
1 = 8O1
2 = 8E1
3018
RW
Start-up delay "t" dur-
ing device start
UINT 16
s
0 …10
3019
RW
Response delay "ton"
for relays "K1" and "K2"
UINT 16
s
0 … 99
3020
RW
Delay on release "toff"
for relays "K1" and "K2"
UINT 16
s
0 … 99
3021
RW
Repetition time "test"
for automatic
device test
UINT 16
---
0 = OFF
1 = 1
2 = 24 h
3022
RW
Reserved
---
---
---
3023
RW
System and function
selection
UNIT 16
---
0=GEn
1 = dc
2 = CHd
3024
RW
Test of the system con-
nection during device
test "nEt"
UINT 16
---
0 = Inactive
1 = Active
3025
RW
Device test during
device start "S. Ct"
UINT 16
---
0 = Inactive
1 = Active
3026
RW
Request stop mode (0
= deactivate device)
UINT 16
---
0 = Stop
1 = ---
3027
RW
Alarm assignment of
relay 1 "r1"
UINT 16
---
Bit 9 … Bit 1
see
3028
RW
Alarm assignment of
relay 2 "r2"
UINT 16
---
Bit 9 … Bit 1
see
8003
WO
Factory settings for all
parameters
UINT 16
---
0x6661 "fa"
8004
WO
Factory setting only
for parameters resetta-
ble by FAC
UINT 16
---
0x4653 "FS"
8005
WO
Start device test
UINT 16
---
0x5445 "TE"
8006
WO
Clear fault memory
UINT 16
---
0x434C "CL"
Regpage
31ister
Property
Description
Format
Unit
Value range