7.3. Fuses F1, F2
The changeover and monitoring module UMA is equipped with two fuses (F1, F2) as a short circuit
protection of the ATICS® unit.
If one of the fuse is tripped, there may be a defect in the changeover module. These fuses
should only be replaced after consulting the Bender Service department.
Technical data of the fuses
Tripping current
4A, slow acting
Breaking capacity
10kA
ELU Type
189140
Dimensions
6,25 x 32mm
Optional the changeover and monitoring module UMA can be equipped with an additional 2-pole circuit
breaker F3. This breaker protects an 230V auxiliary output for supplying alarm and control panels (e.g. FM-
, TM-, TCP-series) An overload or short circuit situation will trip this breaker. The 230V auxiliary output is
provided on terminal.
Please refer to the attached individual, job or project related documentation like wiring diagram
and elevation drawing.