3.3. Features of the UMA710
…
The ATICS® transfer switching device has the following features:
Continuous monitoring of the internal electronic and the circuitry with automatic alarm
Preventive safety due to an automatic reminder of mandatory testing procedures
Maximum reliability of the switching
o
Patented switching system with mechanical and electrical interlocking
o
Short circuit proof contacts with the mechanic of a moulded case circuit breaker
o
Insensitive to voltage fluctuation and vibration due to stable switch position and permanent
contact pressure
Easy to use and a good overview due to a clear menu structure and user interface
The right information at the right time with clear alarm text and a backlit graphic display as well as
via the BMS bus
Can manually be operated and can be locked for maintenance in position “0”
Automatic logging of events e.g. switching, testing, parameter changes
External functional test or replacement of the ATICS® via an optional bypass switch
The ATICS® switch is pluggable
Electronic and switching elements all in one enclosure respectively on a mounting rack
Chang over and IT-System monitoring in one unit
Optional bypass switch
Communication of components with one another via BMS bus
Communication with remote alarm indicator and test combinations and TM alarm indicator and
operator panels via BMS bus
Can be used in systems in accordance with IEC 60364-7-710:2002-11, sections 556.5.2.2, 556.7
and 556.8 and DIN VDE 0100-710 (VDE 0100 Part 710):2002-11, section 710.564.6 with a
changeover period = 15 s or = 0.5 s
Functional Safety according to IEC 61508 for use in special safety environment according to SIL2
Easy field wiring, completely prewired and type tested assembly
The UMA710 module is a configured unit and is only certified and tested in this assembly. Do
not make any changes to the components, their password-protected settings or the wiring
without consulting Bender first. In each case you should make the settings that are required for