ATICS-DIO_D00080_03_M_XXEN / 04.2021 51
ATICS-…-DIO
Press " " button to display the current alarm:
• Line 1: ALARM
– xx = serial number of the displayed alarm
– yy = number of pending messages
• Line 2: Alarm status and alarm text
• Line 3: Measured value
• Line 4: Address and channel of the indicator device
Use the arrow buttons " , " to select previous or next message.
If no button is pressed for a few seconds, the standard display reappears.
Press " " button again to return to the main menu.
i
The alarm text displayed in case of failure of one line depends on the setting in the "System" menu in
the „Settings menu 1: Changeover“ on p. 67.
If individual alarm messages are programmed on a TM… alarm indicator and operator panel or a
CP9xx or an MK… alarm indicator and test combination, the display of this device may differ from
the display of the ATICS®.
6.2.3 Test function
A test is used to check the device function. There are several ways to call up the test menu:
• Select standard display and then press the "TEST" button on the front panel of the device for
at least one second
• Call up "TEST" mode on the Control menu
A test on the changeover function can also be triggered via a digital input (function similar to "Manual
changeover"). Test menu:
Menu item
Function
Page
1. Autom. changeover
Test of the changeover function. Switches back automatically after time
t(test).
2. Manual changeover
Test of the changeover function. Switches back after pressing the "RE-
SET" button.
3. Last changeover
Save last changeover as test
4. Generator
Start generator without switching over. Terminate test by pressing the
"RESET" button.
5. Test communication
Communication test via the BMS bus. To do this, simulate an alarm and
send an alarm message via the BMS bus.
228 V
50 . 0Hz
0 . 00 V
0Hz
12 : 23
Undervoltage
1
2
0
Undervoltage
0 V
Addr. : 3 Chan: 2
ALARM
xx / yy
Exit
1. Autom. changeover
2. Manual changeover
3. Last changeover
Содержание ATICS Series
Страница 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Страница 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Страница 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Страница 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Страница 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Страница 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Страница 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Страница 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Страница 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...
Страница 99: ...ATICS DIO_D00080_03_M_XXEN 04 2021 99 ATICS DIO 10 2 T V test report according to VDE 0100 Part 710...
Страница 100: ...100 ATICS DIO_D00080_03_M_XXEN 04 2021 Technical data 10 3 T V certificate regarding functional safety...