Operation and setting

30

TGH1384en/06.2005

4.4   Menu ISO SETUP: Setting of the basic A-ISOMETER

®

 functions

All alarm functions such as Alarm 1 and Alarm 2 (prewarning and main 
alarm), the operating principle of the alarm relays K1 and K2 (N.O = N/O 
operation, N.C = N/C operation), the fault storage behaviour and a selection 
of two current output ranges are set in this menu.

4.4.1 Response values Alarm 1 and Alarm 2

The response values Alarm 1 and Alarm 2 are selected with the UP/DOWN 
keys and stored with the ENTER key.

4.4.2 Operating principle of the alarm relays

K1/K2 are factory set to N.O Test, that means N/O operation. When the sup-
plement "Test" has been selected, the alarm relays switch over during a man-
ual self test. 
If, for any reason, the alarm relays may not switch over during a manual self 
test, the settings N.C or N.O are to be selected.
K1:  N.C Test = N/C operation contacts 11-12-14, with relay test

(the alarm relay is energized during normal operation)

K1:  N.O Test = N/O operation contacts 11-12-14, with relay test

(the alarm relay is deenergized during normal operation)

K1:  N.C

= N/C operation contacts 11-12-14, without relay test

(the alarm relay is energized during normal operation)

K1:  N.O 

= N/O operation contacts 11-12-14, without relay test

(the alarm relay is deenergized during normal operation)

K1:  Flash 

= Flashing function contacts 11-12-14

(the alarm relay and the LED flash in the event of an alarm

                        message, approximately 0.5 Hz 
K2:  N.C Test = N/C operation contacts 21-22-24, with relay test

(the alarm relay is energized during normal operation)

K2:  N.O Test = N/O operation contacts 21-22-24, with relay test

(the alarm relay is deenergized during normal operation)

K2 : N.C 

= N/C operation contacts 21-22-24, without relay test

(the alarm relay is energized during normal operation)

K2 : N.O 

= N/O operation contacts 21-22-24, without relay test

(the alarm relay is deenergized during normal operation)

K2 : Flash 

= Flashing function contacts 21-22-24

(the alarm relay and the LED flash in the event of an alarm
message, approximately 0.5 Hz)

Содержание A-ISOMETER AGH575S-6

Страница 1: ...A ISOMETER IRDH275BU 6 Coupling device AGH575S 6 Insulation monitoring device for medium voltage IT systems with galvanically connected rectifiers and converters up to AC DC 3 6 kV in combination with...

Страница 2: ...erg Germany Postfach 1161 35301 Gr nberg Germany Tel 49 0 6401 807 0 Fax 49 0 6401 807 259 E mail info bender de com Web server http www bender de com 2005 BENDER Germany All rights reserved Reprintin...

Страница 3: ...warnings 9 1 4 Directions for installation 10 2 Function 11 2 1 Characteristics IRDH275BU 6 incl AGH575S 6 11 2 2 Product description 12 2 3 Function 12 3 Installation and connection 17 3 1 Installat...

Страница 4: ...sure AMP 33 4 5 4 Setting the repitition time for automatic self tests Autotest 24h 33 4 5 5 Setting the real time clock Clock 33 4 5 6 Setting the date Date 33 4 5 7 Specifying the starting time of t...

Страница 5: ...5 3 3 Commissioning of an RS485 network with BMS protocol 43 6 Technical data IRDH275BU 6 with AGH575S 6 45 6 1 Data in tabular IRDH275BU 6 45 6 2 Data in tabular AGH575BU 6 48 6 3 Standards and appro...

Страница 6: ...Table of Contents 6 TGH1384en 06 2005...

Страница 7: ...uded 1 2 Warranty and liability Warranty and liability claims in cases of damage to persons and property shall be excluded if they are attributable to one or more of the following causes Use of the A...

Страница 8: ...ty which may be sustained as a result of faults or errors in this operating manual 1 2 3 Hazards when handling the A ISOMETER or coupling device The devices are constructed according to the state of t...

Страница 9: ...nnected from the power system for the duration of these tests In order to check the proper connection of the device it is recommended to carry out a functional test Make sure that the basic settings m...

Страница 10: ...lowing factory setting Please check if the basic setting of the A ISOMETER complies with the re quirements of the system to be monitored Onlyoneinsulationmonitoringdevicemaybeusedineachintercon nected...

Страница 11: ...3 B1 Two separately adjustable ranges of the response value100 k 10 M Alarm 1 Alarm 2 Two line LC display Automatic device self test Memory with real time clock to store all alarm messages with date a...

Страница 12: ...e set via the function keys The parameters are indicated on the LC display and are stored in a non volatile memory EEPROM after the setting is completed A microprocessor controlled pulsating AC measur...

Страница 13: ...internal measuring functions the components of the process control such as data and parameter memory as well as the earth connections are checked using the self test functions The progress of the sel...

Страница 14: ...nd date are not set a C clock is flashing in the standard display In the event of a supply voltage failure time and date will be stored for at least thirty days If the 24 V test is activated in the IS...

Страница 15: ...tion input F1 F2 to switch over to the standby mode When the input terminals F1 F2 are bridged the measuring function is stopped and the message STANDBY appears on the display The currently measured v...

Страница 16: ...Function 16 TGH1384en 06 2005...

Страница 17: ...4 43 The connections to the supply voltage shall be provid ed with protective devices to afford protection in the event of a short circuit a 6 A fuse is recommended For the connection to the IT syste...

Страница 18: ...nnection 18 TGH1384en 06 2005 2 5 4 AGH575S 6 3 PE 3 AC 3 6 k V L 0 M 3 DC 3 6 k V DC 3 6 k V 5 A1 A2 L1 L2 AK KE T1 T2 R1 R2 F1 F2 M M A B 11 12 14 21 22 24 IRDH275BU 6 mA 120W K1 K2 1 7 8 9 10 11 12...

Страница 19: ...H575S 6 to PE 7 External TEST button NO contact 8 External RESET button NC contact or wire jumper when the terminals are open the fault message will not be stored 9 STANDBY by means of the function in...

Страница 20: ...Installation and connection 20 TGH1384en 06 2005...

Страница 21: ...meter change moving up in the menu 3 RESET button to delete insulation fault alarms Down key parameter change moving down in the menu 4 MENU key to activate the menu system Enter key confirmation para...

Страница 22: ...t at L insulation fault at L s new measurement has started 3 polarity of the measuring pulse valid bus communication signals H new entry in the memory data base C flashing clock is to be set 4 Message...

Страница 23: ...the table of the status numbers on page 53 COM Setup own bus address Please have the details above on hand if you have a problem and if you con tact BENDER for technical questions Activating the TEST...

Страница 24: ...ub menu item confirming or storing a parameter change and going back to the associated sub menu item or going to the next input area ESC key Returning from a sub menu to the previous menu If you do no...

Страница 25: ...Operation and setting 25 TGH1384en 06 2005...

Страница 26: ...d by the symbol padlock closed the first thing to enter is the correct password before the pa rameters can be changed using the UP DOWN keys Entering the correct password once allows all parameters to...

Страница 27: ...ax 5 F 4 Measure AMP 5 Autotest 24h 6 Clock 19 08 7 Date 01 01 04 8 Test 12 00 1 Exit 2 Alarm1 002 MW 3 Alarm2 500 kW 4 K1 N O 5 K2 N O 6 Memory on 7 M M 0 20 mA Nr 01 Nr 02 Power on 1 Exit 2 Addr 003...

Страница 28: ...Clear all on to delete the memory storage and the ESC key to leave the menu A new entry into the memory is signalled with an H on the display in the standard mode The H will be deleted as soon as the...

Страница 29: ...SO SETUP 4 ISO ADVANCED 5 COM SETUP 6 PASSWORD 7 LANGUAGE 8 SERVICE Nr 01 Nr 08 Power on Nr 01 Nr 08 Clear all off Nr 01 Nr 08 28 08 04 17 43 Nr 02 Nr 08 Clear all off Nr 02 Nr 08 Rmin 010 kW Nr 02 Nr...

Страница 30: ...arm relay is energized during normal operation K1 N O Test N O operation contacts 11 12 14 with relay test the alarm relay is deenergized during normal operation K1 N C N C operation contacts 11 12 14...

Страница 31: ...D 5 COM SETUP 6 PASSWORD 7 LANGUAGE 8 SERVICE 1 Exit 2 Alarm1 100 KW 3 Alarm2 200 KW 4 K1 N O 5 K2 N O 6 Memory off 7 M M 0 20 mA Alarm1 100 KW Alarm2 200 KW K1 N O K2 N O Memory off M M 0 20 mA K1 N...

Страница 32: ...H275BU 6 can be set to 0 20 mA oder 4 20 mA via the menu point M M The maximum load is 500 Function 0 20 mA RF insulation fault I current in mA Function 4 20 mA RF insulation fault I current in mA The...

Страница 33: ...tition of automatic self tests can either be set to 1 hour or to 24 hours or can be deactivated Factory setting 24 h 4 5 5 Setting the real time clock Clock The setting of the real time clock is the t...

Страница 34: ...full hour 4 5 8 Diagram ISO ADVANCED 1 EXIT 2 HISTORY INFO 3 ISO SETUP 4 ISO ADVANCED 5 COM SETUP 6 PASSWORD 7 LANGUAGE 8 SERVICE 1 Exit 2 AGH 575S 6 3 Ce max 10 F 4 Measure AMP 5 Autotest 24h 6 Clock...

Страница 35: ...he bus address is not assigned twice The device is factory set to address 3 and hence acts as a slave 4 6 2 Diagram COM SETUP IfseveralA ISOMETER sareoperatedononeBMSbus theaddresses of other A ISOMET...

Страница 36: ...set with the UP DOWN keys and confirmed with the ENTER key The password can be activated in the menu item 3 Status on by clicking the ENTER key The basic setting is 3 Status off that means that the pa...

Страница 37: ...A ISOMETER to be set to different languages There is the choice of German and English The device menu is not influenced by the language selection 4 8 2 Diagram Language IT SYSTEM R 010 M 1 EXIT 2 HIS...

Страница 38: ...browser viewing program for Internet application and our protocol con verter FTC470XET BMS Ethernet TCP IP are required Remote setting is possible for Response value Alarm 1 100 10 000 k Y1 Response...

Страница 39: ...he BMS bus the BMS bus must be terminated at both ends with a 120 resistor An RS485 network that is not terminated is likely to get instable and may result in malfunctions Only the first and the last...

Страница 40: ...anches 5 2 1 Correct arrangement Three examples for correct arrangement 5 2 2 Wrong arrangement Three examples for wrong arrangement 5 2 3 Wiring A suitable type of cable for the wiring of the RS485 n...

Страница 41: ...odes are identified by a unique address The MASTER scans all other devices on the bus cyclically listens to their signals and then carries out specific commands Bus address 1 must be assigned to the M...

Страница 42: ...aps of more than five subsequent addresses so that all slaves can be scanned by the Master For IRDH275B a BMS address can be selected from the address range 1 30 When assigning the addresses also othe...

Страница 43: ...f the RS485 network or in case of devices without a terminating switch at the end of the bus connect a 120 resistor to the terminals A and B Switch the supply voltage US on Determine one IRDH275B as t...

Страница 44: ...575 Insulation monitoring device 1 30 FTC470 Protocol converter 2 30 EDS47x 12 Insulation fault evaluators localisation 31 60 SMO480 12 Signal converter relay 61 90 EDS47xE 12 Insulation fault evalua...

Страница 45: ...77 286 V Power consumption 14 VA Response values Response value Ran1 Alarm 1 100 k 10 M Response value Ran2 Alarm 2 100 k 10 M Relative percentage error 0 20 Response time tan 5 min Hysteresis 25 Mea...

Страница 46: ...2 N O or N C operation Factory setting Alarm 1 Alarm 2 N O operation Electrical endurance 12 000 switching operations Contact class IIB acc to DIN IEC 60255 part 0 20 Rated contact voltage AC 250 V D...

Страница 47: ...ion flexible with connector sleeve without with plastic sleeve 0 25 2 5 mm2 Conductor sizes AWG 24 12 Protection class internal components DIN EN 60529 IP30 Protection class terminals DIN EN 60529 IP2...

Страница 48: ...sport 40 g 6 ms Vibration resistance IEC 60068 2 6 device in operation 1 g 10 150 Hz Vibration resistance IEC 60068 2 6 during transport 2 g 10 150 Hz Ambient temperature during operation 10 C 55 C St...

Страница 49: ...chnical data IRDH275BU 6 with AGH575S 6 49 TGH1384en 06 2005 6 3 Standards and approvals The A ISOMETER was designed under consideration of the following standards IEC 61557 8 1997 02 IEC 61326 2002 0...

Страница 50: ...a IRDH275BU 6 with AGH575S 6 50 TGH1384en 06 2005 6 4 Characteristic curves Max AC voltage between IT system and PE in the frequency range of 50 Hz 100 1000 10000 0 1 1 10 100 fn Hz Un V IRDH275BU 6 A...

Страница 51: ...IRDH275BU 6 with AGH575S 6 51 TGH1384en 06 2005 Current output 0 20 mA IRDH275BU 6 RF Insulation fault in k I Current output in mA I mA RF kW 100 000 10 000 1 000 100 10 10 15 20 5 0 25 RF 20 mA x 120...

Страница 52: ...DH275BU 6 with AGH575S 6 52 TGH1384en 06 2005 Current output 4 20 mA IRDH275BU 6 RF Insulation fault in k I Current output in mA I mA RF kW 100 000 10 000 1 000 100 10 10 15 20 5 0 25 RF 16 mA x 1200...

Страница 53: ...very hour no periodic self test 7 Language German Language English 8 Password protection not activated Password protection activated 9 AMP measuring principle 10 max filter frequency 0 1Hz max filter...

Страница 54: ...IRDH275BU 6 with AGH575S 6 54 TGH1384en 06 2005 Dimension diagram enclosure IRDH275 DIN rail mounting according to IEC 60715 or Screw mounting by means of a plug in trapezoidal support Order No 99005...

Страница 55: ...Technical data IRDH275BU 6 with AGH575S 6 55 TGH1384en 06 2005 Dimension diagram enclosure AGH575S 6 2 5 3 4 220 mm 200 170 86 11 170 125 22 5 190 7...

Страница 56: ...Dimensions Art No 9620 1421 0 20 mA 96 x 96 mm B 986 841 9620S 1421 0 20 mA 96 x 96 mm B 986 842 6 5 3 Label for modified versions There will only be a label in this field if the A ISOMETER is differe...

Страница 57: ...nt output 4 20 mA 52 D Dimension diagram enclosure AGH575S 6 55 IRDH275 54 Directions for installation 10 Display in the menu mode 22 Display in the standard mode 22 E Explanations of symbols and warn...

Страница 58: ...13 21 RS485 interface 39 S Self test A ISOMETER 21 Serial interfaces 39 Setting the bus address for IRDH275B 35 Setting the date IRDH275B 33 Setting the national language 37 Setting the real time clo...

Страница 59: ......

Страница 60: ...l Ing W Bender GmbH Co KG Londorfer Str 65 35305 Gr nberg Germany Postfach 1161 35301 Gr nberg Germany Tel 49 0 6401 807 0 Fax 49 0 6401 807 259 E Mail info bender de com Internet http www bender de c...

Отзывы: