Installation and connection
19
Legend to wiring diagram:
The wiring diagram before is to be taken by way of example.
1
Supply voltage U
s
(see nameplate) via 6 A fuse
2, 3 Terminals L1, L2 are not connected!
4
Connection to the coupling device AGH575S-6:
connect terminal AK to terminal 5 of the coupling device.
5
Separate connection of
and KE to PE
6
Separate connection of the terminals 3 and 4 of the AGH575S-6 to PE
7
External TEST button (NO contact)
8
External RESET button (NC contact or wire jumper),
when the terminals are open, the fault message will not be stored
9
STANDBY by means of the function input F1, F2:
When the contact is closed, insulation measurement does not take place.
10
Current output, galvanically separated:
0...20 mA or 4...20 mA
11
Serial interface RS485 (termination 120
Ω
resistor)
12
Alarm relay 1; changeover contacts provided
13
Alarm relay 2 (system fault relay); changeover contacts provided
14
Connection of the coupling device to the converter:
Terminal 2 to the mid-point of the DC intermediate circuit