Install the ceramics into the appliance according to these instructions—see pages 17 through to 23.
Refit the glass panel and the decorative strip to cover the screws and retaining clamp—See page 10
Test the operating pressure of the appliance by attaching a pressure gauge to the test point of the appliance. This
connection should take place when the appliance is OFF. Ensure that gas is turned on at the gas meter and purge the air
from the appliance by:
SLIDE CONTROL UNITS:
Push down the control lever fully to the (IGN) position and hold. The spark generator
should spark continuously, ensure the spark is being generated correctly at the pilot
assembly. Continue with this procedure until the air is purged from the appliance and the
pilot is lit. Once lit hold the lever pushed down for up to a further 10-15 seconds. Once the
pilot is established and secure allow the lever to rise to the (LOW) position then lift the
lever to the (HIGH) position. Allow the appliance to run for a minimum period of 5
minutes. Next check that the inlet pressure to the appliance is 20 mbar ±1 mbar. Lift the
lever to the position to turn OFF.
Check the operation of the appliance according to these instructions—see page 16.
Spillage monitoring System
This appliance is fitted with an atmospheric sensing system in the form of an oxygen sensing pilot burner. This is designed
to shut the fire off in the event of products being spilled into the room where the fire is being operated. It is important to
note that this spillage monitoring device should not be disabled or be adjusted by the installer. If the spillage monitoring
device (O.D.S pilot) is replaced it must only be exchanged with a suitable component which is supplied by Be Modern Ltd.
Check the clearance of combustion products
SPILLAGE TEST:
To check for satisfactory clearance
of products of combustion, close all doors and
windows and leave the appliance burning on HIGH
for five minutes. Insert a lit smoke match just into
the gap a the top centre of the fire. It is
recommended that a smoke match holder be used.
All the smoke must be drawn into the flue. If spillage
occurs allow a further 5 minutes and repeat the test.
If spillage still occurs turn off the appliance and seek
expert advice. If an extractor fan is situated in the
room the spillage test should be repeated with the
fan running. If there is a connecting room with an
extractor fan the test should be repeated with all the
doors to that room open and the extractor fan
running.
Slide Lever Adjustment
An adjustment is provided to position the slide control lever fore and aft. This is to ensure that there is clearance
behind the lever to allow it to move freely for a smooth operation. To adjust the lever first loosen the upper and
lower screws.
Now rotate the centre screw to reposition the lever. Winding the screw inwards will move the lever outwards and
vice versa. Once the lever is in the correct position, tighten the upper and lower screws to secure.