Technical Documentation
BLR-CM Modbus
Rev. 05
2018-09
16
User parameters 2
Bit 15
Bit 0
Bit 0
CT Type
1 = X/1A
0 = X/5A
Bit 1
Control
00 = Control ON
01 = Control OFF
10 = Control FREEZE
Bit 2
Control
Bit 3
Reserved
X
X
Bit 4
Start AI
1 = Start
0 = Stop
Bit 5
Status AI
1 = Active
0 = Inactive
Bit 6
Reserved
X
X
Bit 7
Reserved
X
X
Bit 8
Reserved
X
X
Bit 9
Reserved
X
X
Bit 10
Reserved
X
X
Bit 11
Reserved
X
X
Bit 12
Data logger synchronization via DI-data logger
1 = Active
0 = Inactive
Bit 13
Reserved
X
X
Bit 14
Logic of DI-Data logger input
1 = Low-active
0 = High-active
Bit 15
Reserved
X
X
Alarm Output Mask 1 (OM1)
Bit 15
Bit 0
Bit 0
VOLTAGE Alarm (Over- or undervoltage)
1 = Selected
0 = Deselected
Bit 1
I-HIGH Alarm (I secondary > 6A)
1 = Selected
0 = Deselected
Bit 2
I-LOW Alarm
1 = Selected
0 = Deselected
Bit 3
TEMP 1 Alarm
1 = Selected
0 = Deselected
Bit 4
TEMP 2 Alarm
1 = Selected
0 = Deselected
Bit 5
THD-U Alarm
1 = Selected
0 = Deselected
Bit 6
THD-I Alarm
1 = Selected
0 = Deselected
Bit 7
Stage warning Alarm (OPC, SPL)
1 = Selected
0 = Deselected
Bit 8
Faulty stage Alarm
1 = Selected
0 = Deselected
Bit 9
Digital input (HT/NT)
1 = Selected
0 = Deselected
Bit 10
Reserved
X
X
Bit 11
P-Overload Alarm
1 = Selected
0 = Deselected
Bit 12
Q-Overload Alarm
1 = Selected
0 = Deselected
Bit 13
P-Export Alarm
1 = Selected
0 = Deselected
Bit 14
CONTROL Alarm
1 = Selected
0 = Deselected
Bit 15
COS-PHI Alarm
1 = Selected
0 = Deselected