Technical Documentation
BLR-CM Modbus
Rev. 05
2018-09
13
All values can be accessed with function codes 03
hex and
04
hex
.
Address
Value
Words
Type
Unit
1792
WQ inductive – extended counter
2
UINT32
MVarh
1794
WQ inductive – base counter
2
FLOAT
Varh
1796
WQ capacitive – extended counter
2
UINT32
MVarh
1798
WQ capacitive – base counter
2
FLOAT
Varh
1800
WP import – extended counter
2
UINT32
MWh
1802
WP import – base counter
2
FLOAT
Wh
1804
WP export – extended counter
2
UINT32
MWh
1806
WP export – base counter
2
FLOAT
Wh
It is possible to read the work counters already summarized since firmware version 2.7.0. These values can be
accessed with function codes 03
hex and
04
hex
.
Address
Value
Words
Type
Unit
2048
WQ inductive
2
REAL
kVarh
2050
WQ capacitive
2
REAL
kVarh
2052
WP import
2
REAL
kWh
2054
WP export
2
REAL
kWh
3.5
Parameter settings
Parameters, which are set by the user, are stored in various data types. The base addresses and the data type can be
found in the table below.
All values can be accessed with function codes 03
hex
,
04
hex
and 06
hex
.
Address
Value
Words
Type
Unit
512
PT ratio x 10
1
UINT16
-
513
CT ratio x 10
1
UINT16
-
514
User parameters 1
1
UINT16
-
515
Phase correction
1
UINT16
°
517
Nominal voltage L - L
2
UINT32
V
519
Limit max. voltage
1
UINT16
%
520
Limit min. voltage
1
UINT16
%
522
Switching time delay x 10
1
UINT16
s
523
Target cos φ 1 (0..100..200 = i0.00..1.00..c0.00)
1
UINT16
-