5.4 Limiters
5.4.1 V/F Limiter
The V / Hz limit is active during the voltage control phase. It works by limiting the Generator voltage as the frequency falls below the
maximum frequency P.131. This operation can avoid the Generator over-flushing in case of a reduction of speed.
5.4.2 Minimum excitation current: Under Excitation limiter
The limit of minimum excitation current is only active when the Generator is in parallel [digital input 52G (machine in parallel) closed].
It represents the minimum excitation current below which the Generator cannot work.
The relation between output voltage and frequency is:
V(Hz) = P. 100 * Hz
P.131 *
1
P.132
Parameter
Description (short)
Description
P.100
P.130
P.131
Gen. rated voltage
Gen. V/f Min freq
Gen. V/f Max freq
Generator rated voltage [V]
Generator minimum frequency ramp (Hz)
Generator maximum frequency ramp (Hz)
P.132
V/f slope
Generator V/f slope
Parameter
Description (short)
Description
P.002
r.900
r.901
F. UE Lim
OE/UE Lim reg KP
OE/UE Lim reg TI
OE/UE Lim reg TI
OE/UE Lim. Reg. KP
OE/EU Lim. Reg. TI
Machine voltage (%)
Gen. rated V
P. 132
min
freq
max
freq
Gen rated
freq
(Hz)
BELTRAME
CENTRO SERVIZI ENERGIA
Motor
Generator
Q+ (var)
overexcited
underexcited
Iemin
Q-
P (w)