19
5.5.4 Minimum capability: Q- limiter
The curve of minimum capability represents the reac�ve power limit absorbed by the machine. It is determined by interpola�ng 5 data:
5.5.5 Maximum capability: Q+ limiter
The curve of maximum capability represents the reac�ve power limit delivered by the machine. It is determined by interpola�ng 2 data:
• Q+ limit a P=0%
P.170 [%]
• Q+ limit a P=100%
P.171 [%]
Parameter
Description (short)
Description
P.160
P.161
P.162
Q – lim @ P 0%
Q – lim @ P 25%
Q – lim @ P 50%
Limit Q- a P=0%
Limit Q- a P=25%
Limit Q- a P=50%
P.163
P.164
Q – lim @ P 75%
Q – lim @ P 100%
Limit Q- a P=75%
Limit Q- a P=100%
Parameter
Description (short)
Description
P.170
P.171
Q + lim @ P 0%
Q + lim @ P 100%
Limit Q+ a P=0%
Limit Q+ a P=100%
BELTRAME
CENTRO SERVIZI ENERGIA
Motor
Generator
Q+ (var)
overexcited
underexcited
Q-
P (w)
100%
100%
75%
75%
50%
50%
25%
25%
0%
Q+ (var)
overexcited
underexcited
Q-
P (w)
P=100%
P=100%
Motor
Generator
P=0%
P.171