background image

Start /

 Stop

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

C

N

L

NO 15V S+S- P+ P-

T+ T-

A

B

GND

A

B

GND

Figure 4: Connection diagram

For cable terminations, see above connection diagram.

4.7.2  I/O connections

1.

Open the terminal box cover removing the screws (5). Refer to fig-

ure 2 on page 7. Use control screwdriver described under section

4.2 to access terminal blocks.

2.

Connect the appropriate wires according to the terminal block di-

agram and the requirements of section 

Connection assignment

(page 8) given below in section 4.7.3.

3.

Close the terminal box cover.

• For a two-pump connection, wire them through a communication

cable connecting the 2 RS-485 ports at the pumps to terminals 15,

16 & 17.

4.7.3  Connection assignment

• For all electrical connections use heat resistant wires or cable rat-

ed for at least 194°F (90°C). The cables should not touch the mo-

tor housing, the pump or the piping.

• Power and control wires must be run in separate channels.

• Metal conduit for power wiring must only be attached to 1/2” NPT

conduit fitting.

NOTICE:

Cable glands are only available for low voltage wiring to protect

against cable slippage and vapor ingress into the terminal box.

5  System Description

5.1  User interface

9

8

7

6

5

4

2

1

3

Figure 5: User interface diagram

1.

Control mode button

2.

Control mode indicators

3.

Parameter button

4.

Parameter indicators

5.

Setting buttons

6.

Numeric display

7.

Power indicator

8.

Status / Fault indicator

9.

Remote control indicator

Hot Surface:

Burn hazard. During the normal operation, the pump surfa-

ces may be so hot that only the buttons should be touched to

avoid burns.

5.1.1  User interface locking/unlocking

The user interface will automatically lock if no button is pressed for ten

minutes, or if the upper setting button (5) and the parameter button (3)

are pressed for two seconds. See 

User interface

 (page 8).

If a button is pressed when the user interface is locked, the display (6)

shows:

To unlock the user interface, press the upper setting button (5) and the

parameter button (3) for two seconds. The display (6) will show:

Now it is possible to change the pump setting as preferred.

5.2  Functions

The main functions of the pump and control modes are selectable

through the pump user interface and the embedded I/O. Advanced

functions or communication features, can only be set via bus protocol

or the optional Wireless module. See the advanced functions manual at

www.bellgossett.com.

5.2.1  Control mode

Mode

Description

Constant pressure

 

Hset

 

The pump maintains a constant

pressure at any flow demand. The

desired head of the pump can be

set via user interface. See section

6.1.2 Change set point.

5  System Description

8

ecocirc XL Installation, Operation, and Maintenance manual

Содержание ecocirc XL

Страница 1: ...Installation Operation and Maintenance manual ecocirc XL ...

Страница 2: ......

Страница 3: ... connection 7 4 7 2 I O connections 8 4 7 3 Connection assignment 8 5 System Description 8 5 1 User interface 8 5 1 1 User interface locking unlocking 8 5 2 Functions 8 5 2 1 Control mode 8 5 2 2 Night set back mode 9 5 2 3 p T control 9 5 2 4 T Constant temperature control 9 5 2 5 p T control 9 5 2 6 T constant 9 5 2 7 External start stop 9 5 2 8 Analog Input 9 5 2 9 Signal relay 9 5 2 10 Externa...

Страница 4: ... 8 5 Faults causes and remedies 12 9 Other Relevant Documentation or Manuals 13 9 1 Embedded Software and Driver Software License Agreement 13 Table of Contents 2 ecocirc XL Installation Operation and Maintenance manual ...

Страница 5: ...th Part 15 of the FCC Rules Operation is sub ject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including inter ference that may cause undesirable operation This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are de...

Страница 6: ...efficient electronically commutated permanent magnet motor The pump is designed for systems with variable flow rates to opti mize pump operation thus reducing energy consumption The pump can be set to any one of the multiple operating modes available with each designed for a specific application to achieve high performance and maximum energy savings A single pump can handle heating cooling and plu...

Страница 7: ...e sensor for details see section 5 2 10 of this manual Temperature sensor for details see section 5 2 10 of this manual Wireless module RS 485 module 4 Installation Precautions WARNING Observe accident prevention regulations in force Use suitable equipment and protection Always refer to the local and or national regulations legislation and codes in force regarding the selection of the installation...

Страница 8: ...es must be correctly sized Pipe work must not transmit any load or torque to pump flanges Be sure to minimize any pipe strain on the pump Support suction and discharge piping by the use of pipe hangers near the pump Line up the vertical and horizontal piping so that the bolt holes in the pump flanges match the bolt holes in the pipe flanges Do not attempt to spring the suction or discharge lines i...

Страница 9: ...ting assembly from motor housing b pay attention to the magnetic hazard listed before A defective O ring must be replaced An O ring is already availa ble inside the package as spare part 4 Properly align and tighten the four hex head screws 2 that affix the motor to the pump body 4 according to the torque table giv en below in a criss cross pattern M6 90 in lb M8 170 in lb M10 340 in lb CAUTION Ch...

Страница 10: ...ce diagram 1 Control mode button 2 Control mode indicators 3 Parameter button 4 Parameter indicators 5 Setting buttons 6 Numeric display 7 Power indicator 8 Status Fault indicator 9 Remote control indicator Hot Surface Burn hazard During the normal operation the pump surfa ces may be so hot that only the buttons should be touched to avoid burns 5 1 1 User interface locking unlocking The user inter...

Страница 11: ...rential temperature of the pumped media For details refer to the advanced functions manual on www bellgos sett com 5 2 7 External start stop The pump can be started or stopped via an external dry contact or a relay that is connected to terminals 11 and 12 The pump unit is provid ed by default with the terminals 11 and 12 jumpered See Figure 4 on page 8 NOTICE The pump provides 5 VDC through the st...

Страница 12: ...ation occurs Cavitation can damage the internal components 6 1 Configure the pump settings Change the pump settings using one of the following methods User interface Bus communication Wireless communication 6 1 1 Change the communication parameters Change pump communication parameters See User interface page 8 1 Switch off the pump Wait until the power indicator light turns off 2 Switch on the pum...

Страница 13: ...tions manual on www bellgossett com 6 2 2 Activate automatic two pump operation Once the communication cable is connected configure only the lead pump The twin pump submenu for this configuration is available at each power on when the drive is displaying SING which stands for Single Pump The following procedure must be executed during the start up phase of the pump 1 Enter the two pump sub menu wh...

Страница 14: ...utes and then power on If the problem persists contact local B G repre sentative A02 High temperature of the fluid Check water temperature value A03 Automatic speed reduction to prevent inverter over heating Check installation condi tions and rectify status of the system A05 Data memory corrupted Switch off the pump for 5 minutes and then power on If the problem persists contact local B G repre se...

Страница 15: ...s in pump Clean the system Worn out bearing Contact local B G representative 9 Other Relevant Documentation or Manuals 9 1 Embedded Software and Driver Software License Agreement With the purchase of the product the terms and conditions of the li cense for the software embedded on the product are considered ac cepted For more information see license condition on www bellgos sett com 9 Other Releva...

Страница 16: ...d farms In more than 150 countries we have strong long standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise backed by a legacy of innovation For more information on how Xylem can help you go to xyleminc com Xylem Inc 8200 N Austin Avenue Morton Grove Illinois 60053 USA Tel 847 966 3700 Fax 847 965 8379 www bellgossett c...

Отзывы: