background image

Mode

Description

Proportional pressure

2

Hset

Hset

The pump pressure is continuous-

ly increased/decreased depend-

ing on the increased/decreased

flow demand. The maximum head

of the pump can be set via user in-

terface. See section 6.1.2 Change

set point.

Fixed speed control

Max

min

Speed
setpoint

The pump maintains a fixed speed

at any flow demand. The speed of

the pump can be set via user inter-

face. See section 6.1.2 Change set

point.

All the above control modes can be combined with the night mode

function.

5.2.2  Night set back mode

The night set back mode cannot be used in cooling systems.
Prerequisite

• The pump is installed between boiler outlet and system supply.

• The night set back feature is initiated when the pump recognizes a

water temperature change brought about by the boiler or high

level control system.

The night set back mode is active only in combination with:

• Proportional pressure

• Constant pressure

• Constant speed

This function reduces power consumption of the pump to the minimum

when heating system is not running. An algorithm detects the water

temperature change and automatically adjusts the speed of the pump.
The pump returns to the original set point as soon as the system re-

starts.

5.2.3  ∆p-T control

This function adjusts the nominal differential pressure set point accord-

ing to the temperature of the pumped media.
For details refer to advanced functions manual on www.bellgos-

sett.com

5.2.4  T-Constant temperature control

This functional mode changes the speed of the pump in order to main-

tain a constant temperature of the pumped media. It is suitable for

heating systems with fixed system characteristics, for example Domes-

tic Hot Water Systems.
For details, refer to the advanced functions manual on www.bellgos-

sett.com

5.2.5  ∆p-∆T control

This function requires the external temperature probe type KTY83 (see

section 5.2.10 of this manual).
This function adjusts the nominal differential pressure set point de-

pending on the differential temperature of the pumped media. An ex-

ternal temperature sensor Type: KTY83 is required for this functionality

(see section 5.2.10 of this manual for details).
For details, refer to the advanced functions manual on www.bellgos-

sett.com

5.2.6  ∆T constant

This function alters the speed of the pump in order to maintain a con-

stant differential temperature of the pumped media.
For details, refer to the advanced functions manual on www.bellgos-

sett.com

5.2.7  External start/stop

The pump can be started or stopped via an external dry contact or a

relay that is connected to terminals 11 and 12. The pump unit is provid-

ed by default, with the terminals 11 and 12 jumpered. See Figure 4 on

page 8.

NOTICE:

• The pump provides 5 VDC through the start / stop terminals.

• No external voltage must be provided to start / stop terminals.

• The cables connected to terminals 11 and 12 shall not exceed 65

feet in length.

5.2.8  Analog Input

The pump integrates a 0-10 V analog input at terminals 7 and 8. See

terminal diagram figures for changing the setpoint. See Figure 4 on

page 8.
When a voltage input is detected, the pump switches to fixed speed

control mode automatically and starts to run according to the following

diagram:

Vin[V]

Speed

[rpm]

Vset

10

1.5

1.2

min

Max

Setpoint

Figure 6: Voltage input detected

Pump stops at 1.2 V
Pump restarts at 1.5 V

5.2.9  Signal relay

A dry contact relay is provided at terminals 4 and 5. See connection di-

agram, figure 4 on page 8, for location. If there is a fault, the relay con-

tact closes to display a red status light and the error code on the user

interface display. See 

User interface

 (page 8). The relay contact closure

can also be used to energize a remote fault display.

Ratings

• Voltage: 115/208 – 230/1

• Imax < 2 A

5.2.10  External sensors (optional)

The pump can be equipped with a differential pressure sensor and a

temperature sensor according to the following table:

Sensor description

Type

Terminals

Differential pressure

sensor 4-20mA

15 PSI
30 PSI

9 - 10

Temperature sensor

KTY83/121

13 - 14

Pressure sensor setup

1.

Install pressure sensor on the pipe

2.

Connect wires at terminals 9 and 10. See Figure 4 on page 8.

3.

Power the pump on.

4.

Upon startup, the pump detects the sensor and displays the setup

menu.

5.

Select the right sensor model and confirm the selection using the

parameter button (3). See 

User interface

 (page 8).

6.

The pump will run through the startup sequence and automatical-

ly start working in constant pressure mode.

7.

The setpoint can be changed using the settings button (5). See 

User interface

 (page 8).

External temperature sensor setup

The external temperature sensor setup and related control modes are

available only through RS-485 or wireless module connection.
For details refer to advanced functions manual on www.bellgos-

sett.com

5  System Description

ecocirc XL Installation, Operation, and Maintenance manual

9

Содержание ecocirc XL

Страница 1: ...Installation Operation and Maintenance manual ecocirc XL ...

Страница 2: ......

Страница 3: ... connection 7 4 7 2 I O connections 8 4 7 3 Connection assignment 8 5 System Description 8 5 1 User interface 8 5 1 1 User interface locking unlocking 8 5 2 Functions 8 5 2 1 Control mode 8 5 2 2 Night set back mode 9 5 2 3 p T control 9 5 2 4 T Constant temperature control 9 5 2 5 p T control 9 5 2 6 T constant 9 5 2 7 External start stop 9 5 2 8 Analog Input 9 5 2 9 Signal relay 9 5 2 10 Externa...

Страница 4: ... 8 5 Faults causes and remedies 12 9 Other Relevant Documentation or Manuals 13 9 1 Embedded Software and Driver Software License Agreement 13 Table of Contents 2 ecocirc XL Installation Operation and Maintenance manual ...

Страница 5: ...th Part 15 of the FCC Rules Operation is sub ject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including inter ference that may cause undesirable operation This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are de...

Страница 6: ...efficient electronically commutated permanent magnet motor The pump is designed for systems with variable flow rates to opti mize pump operation thus reducing energy consumption The pump can be set to any one of the multiple operating modes available with each designed for a specific application to achieve high performance and maximum energy savings A single pump can handle heating cooling and plu...

Страница 7: ...e sensor for details see section 5 2 10 of this manual Temperature sensor for details see section 5 2 10 of this manual Wireless module RS 485 module 4 Installation Precautions WARNING Observe accident prevention regulations in force Use suitable equipment and protection Always refer to the local and or national regulations legislation and codes in force regarding the selection of the installation...

Страница 8: ...es must be correctly sized Pipe work must not transmit any load or torque to pump flanges Be sure to minimize any pipe strain on the pump Support suction and discharge piping by the use of pipe hangers near the pump Line up the vertical and horizontal piping so that the bolt holes in the pump flanges match the bolt holes in the pipe flanges Do not attempt to spring the suction or discharge lines i...

Страница 9: ...ting assembly from motor housing b pay attention to the magnetic hazard listed before A defective O ring must be replaced An O ring is already availa ble inside the package as spare part 4 Properly align and tighten the four hex head screws 2 that affix the motor to the pump body 4 according to the torque table giv en below in a criss cross pattern M6 90 in lb M8 170 in lb M10 340 in lb CAUTION Ch...

Страница 10: ...ce diagram 1 Control mode button 2 Control mode indicators 3 Parameter button 4 Parameter indicators 5 Setting buttons 6 Numeric display 7 Power indicator 8 Status Fault indicator 9 Remote control indicator Hot Surface Burn hazard During the normal operation the pump surfa ces may be so hot that only the buttons should be touched to avoid burns 5 1 1 User interface locking unlocking The user inter...

Страница 11: ...rential temperature of the pumped media For details refer to the advanced functions manual on www bellgos sett com 5 2 7 External start stop The pump can be started or stopped via an external dry contact or a relay that is connected to terminals 11 and 12 The pump unit is provid ed by default with the terminals 11 and 12 jumpered See Figure 4 on page 8 NOTICE The pump provides 5 VDC through the st...

Страница 12: ...ation occurs Cavitation can damage the internal components 6 1 Configure the pump settings Change the pump settings using one of the following methods User interface Bus communication Wireless communication 6 1 1 Change the communication parameters Change pump communication parameters See User interface page 8 1 Switch off the pump Wait until the power indicator light turns off 2 Switch on the pum...

Страница 13: ...tions manual on www bellgossett com 6 2 2 Activate automatic two pump operation Once the communication cable is connected configure only the lead pump The twin pump submenu for this configuration is available at each power on when the drive is displaying SING which stands for Single Pump The following procedure must be executed during the start up phase of the pump 1 Enter the two pump sub menu wh...

Страница 14: ...utes and then power on If the problem persists contact local B G repre sentative A02 High temperature of the fluid Check water temperature value A03 Automatic speed reduction to prevent inverter over heating Check installation condi tions and rectify status of the system A05 Data memory corrupted Switch off the pump for 5 minutes and then power on If the problem persists contact local B G repre se...

Страница 15: ...s in pump Clean the system Worn out bearing Contact local B G representative 9 Other Relevant Documentation or Manuals 9 1 Embedded Software and Driver Software License Agreement With the purchase of the product the terms and conditions of the li cense for the software embedded on the product are considered ac cepted For more information see license condition on www bellgos sett com 9 Other Releva...

Страница 16: ...d farms In more than 150 countries we have strong long standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise backed by a legacy of innovation For more information on how Xylem can help you go to xyleminc com Xylem Inc 8200 N Austin Avenue Morton Grove Illinois 60053 USA Tel 847 966 3700 Fax 847 965 8379 www bellgossett c...

Отзывы: