background image

Mode of operation

A carrier plate uses adaption to make a positive fit on the spring-return actuator and 

transfers the rotary movement directly to the feedback potentiometer.

Switching points can be freely selected with an adjustment dial. The current switch 

position can be read off at any time.

Application

The auxiliary switch unit is used for signaling the position or for exercising switching 

functions in any given angle setting.

Simple direct mounting

The auxiliary switch unit is connected directly by means of adaption with the hollow 

shaft (LF.., NF..A.., SF..A..) of the actuator. Once it is mounted, the unit is screwed to 

the actuator.

The spindle clamp is  mounted on the bottom side.

Electrical installation

Wiring diagrams

S1 S2

S3

S4 S5

S6

S1

S2

S3

S4

S5

S6

S2A

S1 S2 S3 S4 S5 S6

0...100%

Cable colours:

S1 = violet 

S2 =  red 

S3 = white 

S4 = orange 

S5 = pink 

S6 = grey

S2A-F

Auxiliary switch unit, suitable for the spring return 

actuators NF..A.., SF..A.., LF..

Product features

www.belimo.com

S2A-F • en-gb • 2019-04-12 • subject to changes

2

Отзывы: