background image

Technical data sheet

NM24A-MP

www.belimo.com

NM24A-MP • en-gb • 2020-12-14 • Subject to change

3 / 7

Connection option for a sensor (passive or active sensor or switching contact). The MP actuator serves as 
an analogue/digital converter for the transmission of the sensor signal via MP-Bus to the higher level 
system.

The factory settings cover the most common applications. Single parameters can be modified with the 
Belimo Service Tools MFT-P or ZTH EU.

Simple direct mounting on the damper shaft with a universal shaft clamp, supplied with an anti-rotation 
device to prevent the actuator from rotating.

Manual override with push-button possible (the gear is disengaged for as long as the button is pressed or 
remains locked).

Adjustable angle of rotation with mechanical end stops.

The actuator is overload protected, requires no limit switches and automatically stops when the end stop 
is reached.

The first time the supply voltage is switched on, i.e. at the time of commissioning, the actuator carries out 
a synchronisation. The synchronisation is in the home position (0%).
The actuator then moves into the position defined by the positioning signal.

An adaption can be triggered manually by pressing the "Adaption" button or with the PC-Tool. Both 
mechanical end stops are detected during the adaption (entire setting range).
Automatic synchronisation after pressing the gearbox disengagement button is configured. The 
synchronisation is in the home position (0%).
The actuator then moves into the position defined by the positioning signal.
A range of settings can be adapted using the PC-Tool (see MFT-P documentation)

Accessories

Gateways Description

Type

Gateway MP zu BACnet MS/TP

UK24BAC

Gateway MP to KNX

UK24EIB

Gateway MP to Modbus RTU

UK24MOD

Electrical accessories Description

Type

Positioner for wall mounting

CRP24-B1
EXT-WR-FP20-MP

Feedback potentiometer 10 kΩ add-on

P10000A

Feedback potentiometer 1 kΩ add-on

P1000A

Feedback potentiometer 140 Ω add-on

P140A

Feedback potentiometer 200 Ω add-on

P200A

Feedback potentiometer 2.8 kΩ add-on

P2800A

Feedback potentiometer 5 kΩ add-on

P5000A

Feedback potentiometer 500 Ω add-on

P500A

Auxiliary switch 1 x SPDT add-on

S1A

Auxiliary switch 2 x SPDT add-on

S2A

Positioner for wall mounting

SGA24

Positioner for built-in mounting

SGE24

Positioner for front-panel mounting

SGF24

Signal converter voltage/current 100 kΩ Supply AC/DC 24 V

Z-UIC

Connection cable 5 m, A: RJ11 6/4 ZTH EU, B: 6-pin for connection to service socket ZK1-GEN
Connection cable 5 m, A: RJ11 6/4 ZTH EU, B: free wire end for connection to MP/
PP terminal

ZK2-GEN

MP-Bus power supply for MP actuators

ZN230-24MP

Mechanical accessories Description

Type

Angle of rotation limiter for K-NA and K-SA

20334-00001

Actuator arm for standard shaft clamp (one-sided)

AH-25

Shaft extension 240 mm Ø20 mm for damper shaft Ø 8...22.7 mm

AV8-25

Shaft clamp one-sided, clamping range Ø8...26 mm with insert, Multipack 20 pcs. K-ENMA
Shaft clamp one-sided, clamping range Ø8...26 mm, Multipack 20 pcs.

K-ENSA

Converter for sensors

Configurable actuators

Simple direct mounting

Manual override

Adjustable angle of rotation

High functional reliability

Home position

Adaptation and synchronisation

Содержание NM24A-MP

Страница 1: ...nicative control MP Bus Operating range Y 2 10 V Input Impedance 100 k Operating range Y variable Start point 0 5 30 V End point 2 5 32 V Options positioning signal Open close 3 point AC only Modulati...

Страница 2: ...solation or aggressive gases interfere directly with the device and that it is ensured that the ambient conditions remain within the thresholds according to the data sheet at any time Only authorised...

Страница 3: ...osition defined by the positioning signal A range of settings can be adapted using the PC Tool see MFT P documentation Accessories Gateways Description Type Gateway MP zu BACnet MS TP UK24BAC Gateway...

Страница 4: ...ration for flat installation ZG NMA Service tools Description Type Adapter for Service Tool ZTH MFT C Belimo PC Tool Software for adjustments and diagnostics MFT P Service Tool with ZIP USB function f...

Страница 5: ...Functions with basic values conventional mode Override control with AC 24 V with relay contacts Override control with AC 24 V with rotary switch Control remotely 0 100 with positioner SG Minimum limi...

Страница 6: ...relay contacts Override control and limiting with AC 24 V with rotary switch 1 Caution This function is only guaranteed if the start point of the operating range is defined as min 0 5 V Control open...

Страница 7: ...rawings Clamping range Option Accessory K NA Option Shaft clamp mounted below accessories K NA needed Min 40 Min 20 Further documentation Overview MP Cooperation Partners Tool connections Introduction...