background image

Wiring Diagrams

INSTALLATION NOTES

Provide overload protection and disconnect as required.

Actuators may be connected in parallel. Power consumption and input 

impedance must be observed.

Actuators may also be powered by 24 VDC.

Only connect common to negative (-) leg of control circuits.

A 500 

 resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 

to 10 VDC.

16

Actuators are provided with a numbered screw terminal strip instead of 

a cable.
Meets cULus requirements without the need of an electrical ground 

connection.

!

WARNING! LIVE ELECTRICAL COMPONENTS!

During installation, testing, servicing and troubleshooting of this 

product, it may be necessary to work with live electrical components. 

Have a qualified licensed electrician or other individual who has been 

properly trained in handling live electrical components perform these 

tasks. Failure to follow all electrical safety precautions when exposed to 

live electrical components could result in death or serious injury.

 

Control Signal

  (+)

VDC/mA

(–)

Feedback Signal

  (+)

2 to 10 VDC

(–)

 

Ω 

500

Line
Volts

1

3

5

16

7

 

Ω 

24 VAC Transformer

(1)

(2)

(3)

(5)

Common

Hot  +

Y Input, 2 to 10V

U Output

2

2 to 10 VDC / 4 to 20 mA Control

LRB24-SR-T

Modulating, Non-Spring Return, 24 V, for 2 to 10 VDC or 4...20 mA

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Date created, 05/01/2019 - Subject to change. © Belimo Air

controls (USA), Inc.