Wiring Diagrams
INSTALLATION NOTES
Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption and input
impedance must be observed.
Actuators may also be powered by 24 VDC.
Only connect common to negative (-) leg of control circuits.
A 500
Ω
resistor (ZG-R01) converts the 4 to 20 mA control signal to 2
to 10 VDC.
16
Actuators are provided with a numbered screw terminal strip instead of
a cable.
Meets cULus requirements without the need of an electrical ground
connection.
!
WARNING! LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.
Control Signal
(+)
VDC/mA
(–)
Feedback Signal
(+)
2 to 10 VDC
(–)
Ω
500
Line
Volts
1
3
5
16
7
Ω
24 VAC Transformer
(1)
(2)
(3)
(5)
Common
Hot +
Y Input, 2 to 10V
U Output
2
2 to 10 VDC / 4 to 20 mA Control
LRB24-SR-T
Modulating, Non-Spring Return, 24 V, for 2 to 10 VDC or 4...20 mA