Quick adressing
1. Press the “Address” button until the green “Power” LED is no longer illuminated.
LED flashes in accordance with the previously set address.
2. Set the address by pressing the “Address” button the corresponding number of
times (1...16).
3. The green LED flashes in accordance with the address that has been entered
(...16). If the address is not correct, then this can be reset in accordance with Step 2.
4. Confirm the address setting by pressing the green “Adaption” button.
If no confirmation occurs for 60 seconds, then the address procedure is ended. Any
address change that has already been started will be discarded.
The resulting BACnet MS/TP and Modbus RTU address is made up of the set basic
address plus the short address (e.g. 100+7=107).
Service Tools connection
The actuator can be parametrised by ZTH EU via the service socket.
For an extended parametrisation the PC tool can be connected.
AC 24 V
DC 24 V
1
2
+
~
–
T
3
5
6
7
MFT
D+
D
–
BELIMO
PC-Tool
USB
MP
US
B
i
esc
OK
ZTH EU
Dimensions [mm]
Spindle length
L
Min. 52
Min. 20
Clamping range
22...26.7
12...18
12...22
12...18
Dimensional drawings
56
179
70
116
143
36
41
4
Further documentation
• Tool connections
• Description Protocol Implementation Conformance Statement PICS
• Description Modbus register
• Overview MP Cooperation Partners
• MP Glossary
• Introduction to MP-Bus Technology
GM24A-MOD
Rotary actuator, modulating, communicative, hybrid, AC/
DC 24 V, 40 Nm
Service
www.belimo.com
GM24A-MOD • en-gb • 2020-04-21 • subject to changes