background image

 

 

 

 

 

 

 
NFPA 80 (Fire) & NFPA 105 (Smoke) 

 
See NFPA 80 & NFPA 105 for details.  The damper cleaning and examination 
check list here is based on them. 

 
Damper installation shall meet code requirements.  Fire stopping and drywall integrity shall be 
confirmed.  Damper blades shall be in plane of wall.  Duct shall be fall away with no fasteners 
connected to damper sleeve. 
 
a.  Dampers and ducts shall be cleaned of all foreign debris and dust build-up.   
b.  All exposed moving parts of the damper shall be dry lubricated as required by the 

manufacturer.  Do not use oil as it draws dirt. 

c.  Damper shall be examined without defective old motor or new actuator to determine: 

i.  The damper shall fully close from the open position. 

ii.  Damper shall fully open from the closed position. 

iii.  There are no obstructions to the operation of the damper. The damper shall not be 

blocked from closure in any way due to rusted, bent, misaligned, or damaged 
frame or blades.  The damper shall not have defective hinges, side &/or blade 
seals, or other moving parts.  The damper frame shall not be penetrated by any 
foreign objects that would affect operation.  

d.  If the damper is equipped with a fusible link, the link shall be removed for testing to 

ensure full closure and lock-in-place if so equipped. If the link is damaged or painted, it 
shall be replaced with a link of the same size, temperature, and load rating. 

e.  The fusible link shall be reinstalled after testing is complete.  
 
After installation and wiring of new actuator it shall be tested. 

a.

  The checklist may be customized using material here and in NFPA Standards.  Multiple 

geometric configurations of springs, fusible link, thermal sensor(s), and actuation are 
possible.  Confirm with AHJ if any additional requirements exist. 

b.

  Electric thermal sensors, if present, must be tested and replaced if defective.   

c.

  The test shall be conducted with normal HVAC airflow. 

d.

  When equipped with smoke detection activation, the smoke detector shall be activated 

and damper operation observed. 

         A record of all repairs must be kept and made available to AHJ.   

 

 
For the Air Movement and Control Association damper maintainance manual go to: 

http://www.amca.org/publications/damper_maintenance.aspx

 

  

 

NFPA requires damper inspection and repair of dampers.   
See 

www.nfpa.org

. for Standards.  Details not covered here. 

 

Test voltage input to actuators and repair as necessary if voltage is not correct.  
Old breakers often deliver below 115V and failed actuators may be due to power 
supply problems.

 

Ruskin Phillips P150 to Belimo FSNF or FSAF         March 2018 

Содержание FSAF

Страница 1: ...Auxiliary Switches 14 Wiring 16 Building Official Fire Marshal Notification Form 18 Contacts Chris Sheehan 203 749 3112 Larry Felker 775 355 2461 775 250 4160 Cell Mike Knipple 203 749 3170 Laure Pom...

Страница 2: ...local Fire Marshal and or Building Official must be consulted if any blade or auxiliary switches are employed and are connected to the fire alarm system or to a Fire Fighters Smoke Control System FSC...

Страница 3: ...hall be removed for testing to ensure full closure and lock in place if so equipped If the link is damaged or painted it shall be replaced with a link of the same size temperature and load rating e Th...

Страница 4: ...replacement actuator shall have the same voltage rating as the original Amperage the replacement actuator s shall not draw more amperage than the original s and cause the total connected amp draw on a...

Страница 5: ...ce with a modern Belimo with a spring either of two changes may be necessary One if a thermal sensor exists the old spring must be removed or disconnected Make sure the spring cannot jam any part of t...

Страница 6: ...leg kit and mount with bolts Attach crank arm and ball joint beforehand if most expedient 6 Attach ball joint on jackshaft arm and connect SH8 rod Fiddle with the parts and rotation until close Make...

Страница 7: ...ace it The shaft spring was not disconnected The MA418 failed due to high holding torque load against its own internal spring and the external shaft spring Note on sensor wiring When a number of dampe...

Страница 8: ...weld clamp onto shaft FSAF mounts the same Depending on the geometry any number of mounting arrangements are correct Direct coupling is easiest and most Alternately the anti rotation strap can be att...

Страница 9: ...Figure 1 Figure 2 Figure 3 Note how the pin of the anti rotation strap is mounted in middle of actuator U slot This is acceptable as long as mechanically solid Belimo linkage kits https www belimo com...

Страница 10: ...ap may be bent to fit height FSTF Best solution for small dampers where the HW bracket has been hung out into the air is to use an FSTF actuator FSLF direct coupled with old motor and linkage removed...

Страница 11: ...Linkage mounting TYPICAL MECHANICAL DETAILS Ruskin Phillips P150 to Belimo FSNF or FSAF March 2018 11...

Страница 12: ...joint Slot width 1 4 KH 8 Zinc plated steel For shafts 3 8 to 11 16 Uses KG8 90 degree or KG10A ball joint Slot width 21 64 Where the crank arm on the jackshaft is broken or not of the type needed the...

Страница 13: ...y the actuator or rod to shaft is in front of blade ZG DC2 Damper blade clip and ball joints typically used for 6 wide blade control dampers Typically the ctuator or rod to shaft is above or below the...

Страница 14: ...ernately the TS150 may be replaced It is the dual sensor for reopenable dampers http www ruskin com catalog servefile aspx id 797 Auxiliary Switches Where the original switches for signaling position...

Страница 15: ...re colors vary among actuators Belimo Mechanical FSLF FSNF strap threaded connector Chase nipple 2x 4 box and blank cover Existing flex connector and incoming power wires 165F Thermodisc rotation Anti...

Страница 16: ...Use it as a basis for any of the other wiring schematics Note that the alarm connections are not touched when replacing an actuator This is a major concern for Fire Marshals The drawing below is typi...

Страница 17: ...hes for position indication to FSCS The auxiliary switches are used to provide status indication to the fire fighters smoke control panel Typically there are two or three status lights or leds This wi...

Страница 18: ...ke detector or relay contacts Actuator springs damper closed b Reconnect power Actuator drives damper open c Trip thermal sensor Actuator springs damper fully closed d Press manual reset Actuator driv...

Отзывы: