Installation Instructions

Mechanical Installation

Determining Torque Loading and Actuator Sizing

Damper torque loadings, used in selecting the correct size actuator, should be 
provided by the damper manufacturer.  If this information is not available, the 
following general selection guidelines can be used.

Damper Type

Torque Loading

Opposed blade, without edge seals,
for non-tight close-off applications

3 in-lb/sq. ft.

Parallel blade, without edge seals,
for non-tight close-off applications

4 in-lb/sq. ft.

Opposed blade, with edge seals,
for tight close-off applications

5 in-lb/sq. ft.

Parallel blade, with edge seals,
for tight close-off applications

7 in-lb/sq. ft.

The above torque loadings will work for most applications with 1000 FPM face 
velocity.  For applications between this criteria and 2500 FPM, the torque loading 
should be increased by a multiplier of 1.5.  If the application calls for higher criteria
up to 3000 FPM, use a multiplier of 2.0.

Torque Loading Chart

General Information

Belimo actuators should be mounted indoors in a dry, relatively clean environment 
free from corrosive fumes.  If the actuator is to be mounted outdoors, a protective 
enclosure must be used to shield the actuator.
For new construction work, 

order dampers with extended shafts

.  Instruct the

installing contractor to allow space for mounting and service of the Belimo actuator on
the shaft.  The damper shaft must extend at least 4-3/4” from the duct.  If the shaft 
extends less than 4-3/4” or if an obstruction blocks access, the shaft can be extended 
with the AV 8-25 shaft extension accessory or the actuator may be mounted in its short 
shaft configuration.

Mechanical Operation

The actuator is mounted directly to a damper shaft up to 1.05” in diameter by 
means of its universal clamp.  A crank arm and several mounting brackets are 
available for applications where the actuator cannot be direct coupled to the damper
shaft.  The EFB, EFX series actuators provide true spring return operation for reliable
fail-safe application and positive close-off on air tight dampers. The spring return 
system provides constant torque to the damper with, and without, power applied to 
the actuator.  The EFB…-S, EFX…-S versions are provided with two built-in
auxiliary switches. These SPDT switches are provided for safety interfacing or 
signaling, for example, for fan  start-up. The switching function at the fail-safe position
is fixed at +10°, the other switch function is adjustable b10° to +85° (for 
NEMA 4 versions, the second switch is fixed at +85°.)

Automatic Airtight Dampers/Manual Override

The EFB, EFX series provides 95° of rotation and is provided with a graduated
position indicator showing 0° to 95°.

The EFB, EFX has a unique built in manual positioning mechanism which allows the 
setting of any damper position within its 95° of rotation. A pre-tensioned spring 
automatically tightens the damper when power is applied to the actuator,
compensating for damper seal deterioration..

The actuator is shipped at +5° (5° from full fail-safe) to provide automatic 
compression against damper gaskets for tight shut-off. When power is applied, the
manual mechanism is released and the actuator drives toward the full fail-safe
position.  

Y=0

Y=0

Standard Mounting

NOTE:  The EFB, EFX…series actuator is shipped with the manual override 
adjusted for a +5° position at the universal clamp (not at full fail-safe, 0°).
This allows for automatic compression of damper blade seals when the 
actuator is in use, providing tight shut-off. This assumes that the damper is to
have tight shut-off at the fail-safe position. If tight close-off is desired at the 
opposite direction from fail-safe, the manual override should be released so 
the actuator can go to the full fail-safe position. See the manual override 
instructions.

1.  Manually move the damper to the fail-safe position (usually closed).  If the shaft 

rotated counterclockwise (

), this is a CCW installation.  If the shaft rotated

)

clockwise (

), this is a CW installation.  In a CCW installation, the actuator side 

)

marked “CCW” faces out, while in a CW installation, the side marked “CW” faces
out.  All other steps are identical.

2.  The actuator is usually shipped with the universal clamp mounted to the “CCW”

side of the actuator.  To test for adequate shaft length, slide the actuator over the
shaft with the side marked “CCW” (or the “CW” side if this is the side with the
clamp).  If the shaft extends at least 1/8” through the clamp, mount the actuator 
as follows.  If not, go to the 

Short Shaft Installation

 section.

n

3.  If the clamp is not on the correct side as determined in step #1, re-mount the 

clamp as follows.  If it is on the correct side, proceed to step #5.  Look at the
universal clamp. If you are mounting the actuator with the “CCW” side out, 

Torque Loading Chart

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

2

3

4

5

6

7

8

9

10

Torque Loading (in-lb/ sq. ft.)

D

a

m

p

er

 A

rea (

s

q

. f

t.

)

 N40103 - 09/11 - Subject to change.

 © Belimo 

Aircontrols (USA),

 Inc

.

Содержание EFB Series

Страница 1: ...Parallel blade No edge seals Default 2 to 10 VDC Default 150 seconds EFB and EFX Series Spring Return Direct Coupled Actuator A Applications Minimum 270 in lb Torque For damper areas up to 66 sq ft Fo...

Страница 2: ...tion Do it easily with a simple switch modulating actuators Microprocessor controlled brushless DC motor increases actuator life span and reliability provides constant running time modulating actuator...

Страница 3: ...X24 EFX24 S On Off Spring Return 24 V Technical Data EFB24 EFB24 S EFX24 EFX24 S Power supply 24 VAC 20 50 60 Hz 24 VDC 20 10 Power consumption running 9 5 W holding 4 5 W Transformer sizing 16 VA cla...

Страница 4: ...ed and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and...

Страница 5: ...Centered Field Selectable EF_NEMA4_dims EFB24 N4 EFB24 S N4 EFX24 S N4 H NEMA 4 On Off Spring Return 24 V Technical Data EFB24 N4 EFB24 S N4 EFX24 S N4 H Power supply 24 VAC 20 50 60 Hz 24 VDC 20 10 P...

Страница 6: ...red under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Dam...

Страница 7: ...1 05 Centered Field Selectable EF_NEMA2_dims Technical Data EFB120 EFB120 S EFX120 EFX120 S Power supply 100 240 VAC 10 20 50 60 Hz 100 125 VDC 10 Power consumption running 9 5 W holding 4 5 W VA rat...

Страница 8: ...tors shall be cULus approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provid...

Страница 9: ...8 3 K9 2 supplied 1 2 Field Selectable 3 4 Centered Default 1 05 Centered Field Selectable EF_NEMA4_dims Technical Data EFB120 S N4 EFX120 S N4 H Power supply 100 240 VAC 10 20 50 60 Hz 100 125 VDC 1...

Страница 10: ...and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo EFB120 S N4 EFX120 S N4 Load L W066_EFB X 120_N4_11 On Off wiring Wht Blk EFB120...

Страница 11: ...sions Inches mm 4 74 120 5 3 15 80 1 06 27 0 19 4 85 0 53 13 5 5 43 138 4 41 112 0 59 15 2 76 70 1 38 35 0 52 13 3 7 40 188 1 97 50 0 20 5 2 5 63 143 0 33 8 3 2 13 54 2 44 62 11 32 287 5 13 09 332 5 1...

Страница 12: ...d under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Damag...

Страница 13: ...from full fail safe to provide automatic compression against damper gaskets for tight shut off Dimensions Inches mm 4 74 120 5 3 15 80 1 06 27 0 19 4 85 0 53 13 5 5 43 138 4 41 112 0 20 5 2 5 43 138 0...

Страница 14: ...ernational Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Damage Actuators may be c...

Страница 15: ...onfiguration Default parameters for 2 to 10 VDC applications of the EFB24 MFT EFX24 MFT actuator are assigned during manufacturing If required custom versions of the actuator can be ordered The parame...

Страница 16: ...Insulation so an electrical ground is not required to meet agency listings Actuators shall be cULus Approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control...

Страница 17: ...H actuator are assigned during manufacturing If required custom versions of the actuator can be ordered The parameters noted in the Technical Data table are variable These parameters can be changed b...

Страница 18: ...ed to meet agency listings Actuators shall be cULus Approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by...

Страница 19: ...ot on the correct side of the actuator mount it onto the correct side 3 Slide the actuator onto the shaft and tighten the nuts on the V bolt with a 13mm wrench to 11 ft lb of torque 4 Slide the anti r...

Страница 20: ...03 791 8396 LATIN AMERICA CARIBBEAN 38 Installation Instructions K9 2 Universal Clamp 1 2 3 4 1 05 3 4 1 05 1 2 11 16 1 2 3 4 1 2 11 16 1 2 stainless steel 18 5 ft lb 11 ft lb 13mm N40103 09 11 Subjec...

Страница 21: ...r example for fan start up The switching function at the fail safe position is fixed at 10 the other switch function is adjustable between 10 to 85 for NEMA 4 versions the second switch is fixed at 85...

Страница 22: ...using the remaining retainer clip 4 Verify that the damper is still in its full fail safe position 5 Slide the actuator over the shaft 6 Position the actuator in the desired location 7 Tighten the tw...

Страница 23: ...here a damper has a designed rotation less than 90 An example would be a 45 or 60 rotating damper The other application would be to set a minimum damper position which can be easily set or changed wit...

Страница 24: ...tion Without Power The actuator damper installation may be tested without power at the actuator Refer to the manual positioning section of the instructions Move the damper to its full non fail safe po...

Страница 25: ...pled mounting applications The KH EFB may also be used to simultaneously direct couple to a damper shaft and provide an additional crank arm connection to a second damper KH EFB For round shafts up to...

Страница 26: ...ops the pulses to the motor when it senses a stall condition The DC motor remains energized and produces full rated torque to the load This helps ensure that dampers are fully closed and that edge and...

Страница 27: ...following rules are followed 1 The transformers are properly sized 2 All No 1 wires from all actuators are tied together and tied to the negative leg of the control signal See wiring diagram Wire Leng...

Страница 28: ...Signal position Actuator operates properly Step 7 Step 5 5 Check input signal with a digital volt meter DVM Make sure the input is within the range of the actuator NOTE The input signal must be above...