85°

Auxiliary Switches for EFB24-MFT-S N4, EFX24-MFT-S N4

W600_EFX_MFT_N4_1

1

W399_11

VDC/4-20 mA

W399_11

PWM

M

W

399_11

On/Off control

Off

l

W

399_11

Floating Point control

Accessories

IND-EFB

Damper position indicator

KH-EFB

Crank arm

K9-2

Universal clamp for up to 1.05” diameter jackshafts

Tool-07

13 mm wrench

ZG-EFB

Crank arm adaptor kit

NOTE:

 When using EFB24-MFT-S N4, and EFX24-MFT-S N4(H) actuators, only use accessories

           listed on this page.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.

Typical Specification

Spring return control damper actuators shall be direct coupled type which require no 
crank arm and linkage and be capable of direct mounting to a jackshaft up to a 1.05” 
diameter. The actuator must provide proportional damper control in response to a 2 to 
10 VDC or, with the addition of a 500

Ω

 resistor, a 4 to 20 mA control input from an 

electronic controller or positioner. The actuators must be designed so that they may be 
used for either clockwise or counterclockwise fail-safe operation.  Actuators shall use
a brushless DC motor controlled by a microprocessor and be protected from overload
at all angles of rotation. Run time shall be constant, and independent of torque. A 2 to
10 VDC feedback signal shall be provided for position feedback. Actuators with 
auxiliary switches must be constructed to meet the requirements for Double 
Insulation so an electrical ground is not required to meet agency listings. Actuators 
shall be cULus Approved and have a 5 year warranty, and be manufactured under ISO 
9001 International Quality Control Standards. Actuators shall be as manufactured by 
Belimo.

Wiring Diagrams

1

Provide overload protection and disconnect as required.

2

CAUTION 

Equipment Damage!

Actuators may be connected in parallel if not mechanically mounted to the same
shaft. Power consumption and input impedance must be observed. 

3

Actuators may also be powered by 24 VDC.

4

Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.

5

Control signal may be pulsed from either the Hot (source) or the Common
(sink) 24 VAC line.

8

Contact closures A & B also can be triacs.
A & B should both be closed for triac source and open for triac sink.

9

For triac sink the common connection from the actuator must be connected 
to the hot connection of the controller.

Meets UL requirements without the need of an electrical ground
connection.

The ZG-R01 500

Ω

resistor may be used.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components.  Have a qualifi ed licensed electrician 
or other individual who has been properly trained in handling live electrical components 
perform these  tasks. Failure to follow all electrical safety precautions when exposed to 
live electrical components could result in death or serious injury.

EFB24-MFT-S N4, EFX24-MFT-S N4(H)

NEMA 4, Proportional, Spring Return, Direct Coupled, 24V, Multi-Function Technology

®

G

K-AF-NF N4H 24V 

hh

ea

ter

NEMA 4 Heater 

 N40103 - 09/11 - Subject to change.

 © Belimo 

Aircontrols (USA),

 Inc.

Содержание EFB Series

Страница 1: ...Parallel blade No edge seals Default 2 to 10 VDC Default 150 seconds EFB and EFX Series Spring Return Direct Coupled Actuator A Applications Minimum 270 in lb Torque For damper areas up to 66 sq ft Fo...

Страница 2: ...tion Do it easily with a simple switch modulating actuators Microprocessor controlled brushless DC motor increases actuator life span and reliability provides constant running time modulating actuator...

Страница 3: ...X24 EFX24 S On Off Spring Return 24 V Technical Data EFB24 EFB24 S EFX24 EFX24 S Power supply 24 VAC 20 50 60 Hz 24 VDC 20 10 Power consumption running 9 5 W holding 4 5 W Transformer sizing 16 VA cla...

Страница 4: ...ed and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and...

Страница 5: ...Centered Field Selectable EF_NEMA4_dims EFB24 N4 EFB24 S N4 EFX24 S N4 H NEMA 4 On Off Spring Return 24 V Technical Data EFB24 N4 EFB24 S N4 EFX24 S N4 H Power supply 24 VAC 20 50 60 Hz 24 VDC 20 10 P...

Страница 6: ...red under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Dam...

Страница 7: ...1 05 Centered Field Selectable EF_NEMA2_dims Technical Data EFB120 EFB120 S EFX120 EFX120 S Power supply 100 240 VAC 10 20 50 60 Hz 100 125 VDC 10 Power consumption running 9 5 W holding 4 5 W VA rat...

Страница 8: ...tors shall be cULus approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provid...

Страница 9: ...8 3 K9 2 supplied 1 2 Field Selectable 3 4 Centered Default 1 05 Centered Field Selectable EF_NEMA4_dims Technical Data EFB120 S N4 EFX120 S N4 H Power supply 100 240 VAC 10 20 50 60 Hz 100 125 VDC 1...

Страница 10: ...and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo EFB120 S N4 EFX120 S N4 Load L W066_EFB X 120_N4_11 On Off wiring Wht Blk EFB120...

Страница 11: ...sions Inches mm 4 74 120 5 3 15 80 1 06 27 0 19 4 85 0 53 13 5 5 43 138 4 41 112 0 59 15 2 76 70 1 38 35 0 52 13 3 7 40 188 1 97 50 0 20 5 2 5 63 143 0 33 8 3 2 13 54 2 44 62 11 32 287 5 13 09 332 5 1...

Страница 12: ...d under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Damag...

Страница 13: ...from full fail safe to provide automatic compression against damper gaskets for tight shut off Dimensions Inches mm 4 74 120 5 3 15 80 1 06 27 0 19 4 85 0 53 13 5 5 43 138 4 41 112 0 20 5 2 5 43 138 0...

Страница 14: ...ernational Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Damage Actuators may be c...

Страница 15: ...onfiguration Default parameters for 2 to 10 VDC applications of the EFB24 MFT EFX24 MFT actuator are assigned during manufacturing If required custom versions of the actuator can be ordered The parame...

Страница 16: ...Insulation so an electrical ground is not required to meet agency listings Actuators shall be cULus Approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control...

Страница 17: ...H actuator are assigned during manufacturing If required custom versions of the actuator can be ordered The parameters noted in the Technical Data table are variable These parameters can be changed b...

Страница 18: ...ed to meet agency listings Actuators shall be cULus Approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by...

Страница 19: ...ot on the correct side of the actuator mount it onto the correct side 3 Slide the actuator onto the shaft and tighten the nuts on the V bolt with a 13mm wrench to 11 ft lb of torque 4 Slide the anti r...

Страница 20: ...03 791 8396 LATIN AMERICA CARIBBEAN 38 Installation Instructions K9 2 Universal Clamp 1 2 3 4 1 05 3 4 1 05 1 2 11 16 1 2 3 4 1 2 11 16 1 2 stainless steel 18 5 ft lb 11 ft lb 13mm N40103 09 11 Subjec...

Страница 21: ...r example for fan start up The switching function at the fail safe position is fixed at 10 the other switch function is adjustable between 10 to 85 for NEMA 4 versions the second switch is fixed at 85...

Страница 22: ...using the remaining retainer clip 4 Verify that the damper is still in its full fail safe position 5 Slide the actuator over the shaft 6 Position the actuator in the desired location 7 Tighten the tw...

Страница 23: ...here a damper has a designed rotation less than 90 An example would be a 45 or 60 rotating damper The other application would be to set a minimum damper position which can be easily set or changed wit...

Страница 24: ...tion Without Power The actuator damper installation may be tested without power at the actuator Refer to the manual positioning section of the instructions Move the damper to its full non fail safe po...

Страница 25: ...pled mounting applications The KH EFB may also be used to simultaneously direct couple to a damper shaft and provide an additional crank arm connection to a second damper KH EFB For round shafts up to...

Страница 26: ...ops the pulses to the motor when it senses a stall condition The DC motor remains energized and produces full rated torque to the load This helps ensure that dampers are fully closed and that edge and...

Страница 27: ...following rules are followed 1 The transformers are properly sized 2 All No 1 wires from all actuators are tied together and tied to the negative leg of the control signal See wiring diagram Wire Leng...

Страница 28: ...Signal position Actuator operates properly Step 7 Step 5 5 Check input signal with a digital volt meter DVM Make sure the input is within the range of the actuator NOTE The input signal must be above...

Отзывы: