•  Outdoor application: only possible in case that no (sea)water, snow, ice, insolation 

or aggressive gases interfere directly with the actuator and that is ensured that the 

ambient conditions remain at any time within the thresholds according to the data 

sheet.

•  Only authorised specialists may carry out installation. All applicable legal or 

institutional installation regulations must be complied during installation.

•  The switch for changing the direction of motion and so the closing point may be 

adjusted only by authorised specialists. The direction of motion is critical, particularly 

in connection with frost protection circuits.

•  The device may only be opened at the manufacturer’s site. It does not contain any 

parts that can be replaced or repaired by the user.

•  Cables must not be removed from the device.
•  The device contains electrical and electronic components and must not be disposed 

of as household refuse. All locally valid regulations and requirements must be 

observed.

Product features

Mode of operation

The actuator moves the valve to the desired operating position at the same time as 

the integrated capacitors are loaded. Interrupting the supply voltage causes the valve 

to be moved to the selected emergency setting position (POP) by means of stored 

electrical energy.

Pre-charging time (start up)

The capacitor actuators require a pre-charging time. This time is used for charging the 

capacitors up to a usable voltage level. This ensures that, in the event of an electricity 

interruption, the actuator can move at any time from its current position into the preset 

emergency setting position (POP). The duration of the pre-charging time depends 

mainly on how long the power was interrupted.

[d] = Electricity interruption in days 

[s] = Pre-charging time in seconds

Typical pre-charging time

0

1

2

7

≥10

 

6

9

11

16

20

0

0

5

10

15

20

25

30

0

5

10

15

20

25

30

2

4

6

8

10

12

[d]

[s]

[s]

[s]

[d]

Delivery condition (capacitors)

The actuator is completely discharged after delivery from the factory, which is why the 

actuator requires approximately 20 s pre-charging time before initial commissioning in 

order to bring the capacitors up to the required voltage level.

Simple direct mounting

Simple direct mounting on the globe valve by means of form-fit hollow clamping jaws. 

The actuator can be rotated by 360° on the valve neck.

Manual override

Manual control with push-button possible - temporary. The gear is disengaged and the 

actuator decoupled for as long as the button is pressed. 

The stroke can be adjusted by using a hexagon socket screw key (5 mm), which 

is inserted into the top of the actuator. The stroke spindle extends when the key is 

rotated clockwise.

High functional reliability

The actuator is overload protected, requires no limit switches and automatically stops 

when the end stop is reached.

AVK230A-3

SuperCap globe valve actuator, 3-point, AC 230 V, 2000 N

Safety notes

www.belimo.eu

AVK230A-3 • en-gb • 2017-03-09 • subject to changes