EMC and immunity
EMC compliance – IEC/EN 61000-6-2:2005 EMI TYPE tests,
test acc. to:
A
a)
B
a)
H
a)
IEC/EN 61000-4-2 Electrostatic discharge
Contact discharge
Air discharge
4 kV
8 kV
8 kV
15 kV
8 kV
15 kV
IEC/EN 61000-4-3 Electromagnetic field
80 MHz ... 3000 MHz
10 V/m 20 V/m 20 V/m
IEC/EN 61000-4-4 Fast transients (burst)
Power line
Data line
2 kV
1 kV
4 kV
4 kV
4 kV
4 kV
IEC/EN 61000-4-5 Voltage surges
Power line, line / line
Power line, line / ground
Data line
0.5 kV
1 kV
1 kV
1 kV
2 kV
4 kV
1 kV
2 kV
4 kV
IEC/EN 61000-4-6 Conducted disturbances
10 kHz - 150 kHz
150 kHz ... 80 MHz
3 V
10 V
3 V
10 V
3 V
10 V
EN 61000-4-9
Pulse magnetic fields
—
300 A/m 300 A/m
EMC interference emission
A
a)
B
a)
H
a)
EN 55032
Class A
Yes
Yes
Yes
FCC 47 CFR Part
15
Class A
Yes
Yes
Yes
German Lloyd
Classifi Construction Guidelines VI-
7-3 Part 1 Ed.2001
—
Yes
Yes
Stability
A
a
a. Product code A: Approval = CE, UL
Product code B: Approval = CE, UL, GL, railway (trackside), Substation,
HazLoc/ATEX/IECEx
Produktcode H: Zulassung = CE, UL, GL, Bahn (Gleisbereich), Sub Station
B
a)
H
a)
Vibration
IEC 60068-2-6 Test FC test level according
to IEC 61131-2
Yes
Yes
Yes
Germanischer Lloyd Guidelines for the
Performance of Type Tests Part 1
—
Yes
Yes
IEC 870-2-2 table 3 normal installation
according to EN 61850-3
—
Yes
Yes
Shock
IEC 60068-2-27 Test Ea test level according
to IEC 61131-2
Yes
Yes
Yes
IEC 870-2-2 table 3 normal installation
according to EN 61850-3
—
Yes
Yes