CONNECTIONS AND USER INTERFACE

 

 

1.

 

Alarm LED indicator:

 ON when the unit is in backup. Blinks at 1 Hz rate in case of error. 

2.

 

Modbus RTU over USB:

 Used to connect a PC running POWERMASTER or custom application for remote monitoring 

and controlling. Firmware update is also possible through USB connection. 

3.

 

Temperature sensor:

 Optional temperature sensor (P/N: WNTC-2MT) to measure the battery temperature for 

protection and temperature compensated charge method. 

4.

 

Relays dry contacts:

 2 relays are present for remote monitoring. 

5.

 

Modbus RTU over RS485: 

Used to connect a PC running for remote monitoring and controlling. Firmware update is 

also possible through RS485 connection. 

6.

 

Inhibit input: A voltage between 5 VDC and 30 VDC applied to this input activates the inhibit function. 

7.

 

Auxiliary output supply:

 Maximum 5A supply from the battery (unregulated). 

8.

 

Input connection:

 2 poles are provided for input connection. This must be connected to a power supply rated 12 

 48 

VDC. 

9.

 

Output connection:

 2 poles are provided for output connection. It must be connected to the load to be backed up. 

10.

 

Battery connection:

 2 poles are provided for battery connection. This must be connected to the battery. Please 

respect the correct polarity. 

11.

 

Display area:

 provides information regarding the device status. 

12.

 

Control keys:

 4 push buttons are provided to navigate through the menus and to select the various functions. 

 

 

 

USER INTERFACE

 

SYMBOL 

NAME 

FUNCTION 

 

MENU KEY 

Scrolls between menus. 

 

DOWN KEY 

Scrolls down menus and values. 

 

UP KEY 

Scrolls up menus and values. 

 

OK KEY 

Confirms selection. 

 

INPUT 

The measured input voltage and current is shown in this section. 

 

OUTPUT 

The measured output voltage and current is shown in this section. 

 

BATTERY 

The battery voltage, current, temperature, resistance and charge are shown in this section. During charging and 
discharging the symbol background color changes to orange and the number of bars drawn inside reflects the charge 
status. During discharging and charging an arrow drawn beside the symbol reflects the direction of the current flowing 
through the battery, pointing towards the battery during charging. Battery section is not present in DC-DC mode. 

 

AUXILIARY 

The measured auxiliary output voltage and current is shown in this section. 

 

 

MODE DISPLAYED

 

UPS STATUS SCREEN 

DC/DC STATUS SCREEN 

ALARM SCREEN 

 

 

 

 

Содержание LDD960-UU

Страница 1: ...y out work on live parts Danger of fatal injury The product s enclosure may be hot allow time for cooling product before touching it Do not allow liquids or foreign objects to enter into the products To avoid sparks do not connect or disconnect the device before having previously turned off input power and wait for internal capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN...

Страница 2: ... connected to the load to be backed up 10 Battery connection 2 poles are provided for battery connection This must be connected to the battery Please respect the correct polarity 11 Display area provides information regarding the device status 12 Control keys 4 push buttons are provided to navigate through the menus and to select the various functions USER INTERFACE SYMBOL NAME FUNCTION MENU KEY S...

Страница 3: ...ckup the internal Coulomb counter is used to give an estimate of the residual charge of the battery Backup starts when the output voltage is lower than 90 of the Nominal output voltage Battery charger The battery charger supports various chemistries such Lead Acid Nickel Lithium and Super capacitors Other charging algorithms can be implemented by request contact factory The battery charger automat...

Страница 4: ...ltaneously the buttons until you see the welcome message on the screen On the status screen the Cold start text is written beside the input icon Release the buttons PC shutdown and automatic restart PC shutdown In case the LDD960 UU is used to supply a PC it is possible to automatically shut down the PC after an adjustable time of backup For this the PC must run the POWERMASTER application provide...

Страница 5: ...y SoC 25 Bat SoC 25 Active when the battery State of Charge is under 25 of the nominal full charge capacity Battery over discharge current Bat over dis I Active when the measured battery discharge current reaches the threshold specified in Battery max discharge current field Battery low Bat low Active when the measured battery voltage is under the threshold specified in Battery low voltage field B...

Страница 6: ...wer side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the Installation Instruction of each family MOUNTING 1 Tilt the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hits the stop 4 Press against the bottom for locking 1 2 3 4 DISMOUNTING 1 Pull down the slide clamp lever 2 Tilt the unit upward 3 ...

Отзывы: