LDB120 Series
4
FIG.6 - INPUT PROTECTION
In order to be UL compliant use Listed Cartridge nonrenewable (JDDZ) fuse Class CC 4 AT 250 VAC.
Fuse 4 AT or MCB 4 A C curve.
For USA and Canada, use the fuse type closest to the European equivalent type.
Surge protection:
it is strongly recommended to provide external surge arresters (SPD) according to local regulations.
FIG.7 - INPUT CONNECTIONS
AC LINE
DC LINE
FIG.8 - ENVIRONMENT
OPERATING TEMPERATURE
DERATING
- 40°C to 70°C
5 - 95% r.H. non condensing
Overtemperature protection
UL Certified up to +50°C
- 0.75 W / °C over 50°C for LDB120-12 model
- 1.20 W / °C over 50°C for LDB120-24 model
NOTES:
▪
Data may change without prior notice in order to improve the product.
▪
Please refer to the latest version of the Installation Instruction for each product by visiting
ACCESSORIES
▪
LDX-D20
20 A Active ORing controller
▪
LDX-D50 50 A Active ORing controller
▪
LDX-B20
150J Buffer Module
▪
LDX-L30
Sealed Lead acid Battery pack