INSTALLATION INSTRUCTION 

 

 

Asia-Pacific 

+86 755 298 85888

 

Europe, Middle East 

+353 61 225 977

 

North America 

+1

 

408

 

785 5200

 

© 2020 Bel Power Solutions & Protection

 

BCM.00466_AD

 

 

FIG.1 - CONNECTIONS 

FIG.2 - DIMENSIONS 

FIG.3 - DISTANCES 

 

Just for reference 

(1)

 

AC/DC input 

(2)

 

DC output (load) 

(3)

 

Battery connection 

(4)

 

Diagnostic Output dry contact  

NC load supplied by Power S. 
NO load supplied by Battery 

(5)

 

Green LED: Output on Power S. 

(6)

 

Red LED: output on Battery 

(7)

 

Output voltage adjustment 

 

 

 

 

Input AC Line: 

 

L = Line 

 

N = Neutral 

 

 = Earth ground 

Input DC Line: 

 

L = + Positive DC 

 

N = - Negative DC 

 

= Earth ground 

Output: 

 

LOAD + = Positive DC 

 

LOAD - = Negative DC 

 

BATT + = Positive DC Battery 

 

BATT - = Negative DC Battery 

 

Dry contact = NC 

 

Dry contact = NO 

Dimension 


mm (inc) 

54.0 (2.16) 

110.0 (4.33) 
115.0 (4.52) 

Distance 


mm (inc) 

20 (0.8) 
50 (2.0) 

 
 

FIG.4 - MOUNTING / DISMOUNTING INSTRUCTIONS 

 

For DIN rail fastening according to IEC 60715 TH35-7.5(-15) 
Mounting as shown in figure, with input terminals on lower side, with suitable cooling and maintaining a proper distance between adjacent devices as specified in the 
Installation Instruction of each family. 
 

 

MOUNTING: 

 

1.

 

Tilt the unit slightly backwards. 

2.

 

Fit the unit over the top edge of the rail. 

3.

 

Slide it downward until it hits the stop. 

4.

 

Press against the bottom for locking. 

 

 

 

 

 
 

FIG.5 - RECOMMENDED CONNECTING CABLE 

 

Recommended Tightening torque 

0.5 - 0.6 Nm 
4.42 - 5.30 lbf in 

 

 

 

Solid: 2.5 mm² / 12 AWG 
Stranded:1.5 mm² / 12 AWG 
L: 6.0 - 7.5 mm / 0.24 - 0.30 in 

 
 
 
 
 
 

Содержание LDB120 Series

Страница 1: ...disconnect the device before having previously turned off input power and wait for internal capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN FEUER STROMSCHLAG PERSONENSCHÄDEN Führen Sie niemals Arbeiten an spannungsführenden Teilen durch Gefahr von tödlichen Verletzungen Das Gehäuse des Gerätes kann heiß sein lassen Sie Zeit zum Abkühlen des Gerätes bevor Sie es berühren ...

Страница 2: ...NECTION The device can be connected to single phase AC lines with Vin 120 240 VAC see Fig 7 Please connect first the PE 6 DC INPUT CONNECTION Connect L terminal to positive pole N terminal to negative pole and terminal to GND Rated voltage 110 345 VDC The device is also suitable for photovoltaic or wind turbine applications see Fig 7 7 OUTPUT CONNECTION The device is suitable for SELV and PELV cir...

Страница 3: ...TT Positive DC Battery BATT Negative DC Battery Dry contact NC Dry contact NO Dimension W D H mm inc 54 0 2 16 110 0 4 33 115 0 4 52 Distance A B mm inc 20 0 8 50 2 0 FIG 4 MOUNTING DISMOUNTING INSTRUCTIONS For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent...

Страница 4: ...ONNECTIONS AC LINE DC LINE FIG 8 ENVIRONMENT OPERATING TEMPERATURE DERATING 40 C to 70 C 5 95 r H non condensing Overtemperature protection UL Certified up to 50 C 0 75 W C over 50 C for LDB120 12 model 1 20 W C over 50 C for LDB120 24 model NOTES Data may change without prior notice in order to improve the product Please refer to the latest version of the Installation Instruction for each product...

Отзывы: