OPERATION MANUAL

 

 

 

 

[email protected] 

 

 

 

 

 

MODELS: 
 
LBC8000-1110SxxxG 
LBC12000-1110SxxxG

 

AC INPUT:  

 3 PHASE 

VOLTAGE: 230-277 / 400-480 Vac 3W + PE 
CURRENT: 14-9 A    (LBC8000) 
CURRENT: 21-14 A  (LBC12000) 
FREQUENCY: 50 / 60 Hz 

 

DC OUTPUT: 

 

VOLTAGE: adjustable 80 

 137.5 Vdc 

CURRENT: max. 73 A   (8000 W @ 110 V) 
CURRENT: max. 110 A (12000 W @ 110 V) 

 
 

SAFETY APPROVALS 

 

 

CE Mark

 

 

China  RoHS

 

 

 

 

 

CAUTION 

These  component  level  power  supplies  are  intended exclusively  for installation within other equipment by  an  industrial assemb ly operation or  by 
professional installers. These are Class 1 power supplies; the unit must be properly connected to earth ground in end use. A component power supply 
should be installed in end-use equipment according to the requirements of the safety standard used for that equipment. This power supply is not designed 
to be operated outside of an enclosure which provides a means of mechanical, electrical, and fire protection.

 

PROTECTIVE  EARTHING 

The Power Supply must be properly grounded to mains protective earth termination at end use. 

ENVIRONMENTAL  CONDITIONS: 

TRANSPORTATION & STORAGE:  Ambient Temperature Range -40 °C to +85 °C 

Relative Humidity Range: 5% to 95% RH Non-Condensing 
Altitude: to 12192 m (40 000 feet) ASL 
 

 

OPERATION:  Ambient Temp. Range -25°C to +55°C (at 100% load), to +70°C (at 75% load) 

Relative Humidity Range: 10% to 90% RH Non-Condensing 
Altitude (ASL): to 2500 m full power, to 3048 m (10 000 feet) derating 90% of full power 

INSTALLATION REQUIREMENTS 

Recommended power wires dimensions you can find in charts below. The mate parts of connectors are also described below. For t he air inlet and outlet 
there is required to maintain a minimum open space 10 cm. For chassis fastening you will need 6x screws M8. The preferred mounting position is vertical, 
with connectors on top. The input shall be fused by: Breaker  ABB, S203MT, C16, or similar. The output Battery must be protected by following fusing: 
Breaker ABB, S802S-UCB125 (125A, char. B), or similar. 

WARNING 

1.

 

The equipment is for business use (Class A). In a  domestic environment this product may cause radio interference in which case the user may be 
required to take adequate measures.  

2.

 

The AC Leakage current exceeds 3.5 mA at maximal input voltage and frequency (3 x 528 VAC / 63 Hz). It is necessary to take appropriate measures 
(additional fixed grounding of the chassis). 

3.

 

Do not touch the Output connector X2 during the operation . There is a hazard voltage present, up to 138 Vdc. 

4.

 

Caution, this is a heavy weight unit, 24-30 kg. 

SAFETY INSTRUCTIONS 

Switch off the input power and disconnect battery (X2) together with connector X3, X1 and wait min. 2 minutes before doing any maintenance on the unit! 

SERVICING 

In case of failure, the unit must be returned to the Bel Power Solutions Authorized Service Center. There are no user serviceable parts inside, except of the 
fan replacement. In case of failure of the fan this can be replaced without whole chassis opening. The procedure is described below.  

CORROSION  PROTECTION

 

The unit outside is protected by painting with Soprano 1 

 Art. 095 000298-000. Inside all PC boards are protected by lacquering with Humiseal 1B73. 

LIMITED WARRANTY 

Bel Power Solutions warrants each power supply of its manufacture for a period of two years from the date of original shipment. This warranty applies to 
defects in materials and workmanship that result in non-performance to published specifications. The product(s) must be returned to a Bel Power Solutions 
Authorized Service Center for repair with a Bel Power Solutions pre-assigned RMA number. 
Bel Power Solutions assumes no liabilities for consequential damages of any kind through the use or misuse of its products by  any user. No other obligations 
are expressed or implied.  Please note that the specifications, terms, and conditions stated are subject to change without notice. 

 

 

 

Содержание LBC series

Страница 1: ...reviously turned off input power and wait for internal capacitors discharge minimum2 minutes GEFAHR VON VERBRENNUNGEN EXPLOSIONEN FEUER STROMSCHLAG PERSONENSCHÄDEN Führen Sie niemals Arbeiten an spannungsführenden Teilen durch Gefahr von tödlichen Verletzungen Das Gehäuse des Gerätes kann heiß sein lassen Sie Zeit zum Abkühlen des Gerätes bevor Sie es berühren Lassen Sie keine Flüssigkeiten oder F...

Страница 2: ...reaker ABB S203MT C16 or similar The output Battery must be protected by following fusing Breaker ABB S802S UCB125 125A char B or similar WARNING 1 The equipment is for business use Class A In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures 2 The AC Leakage current exceeds 3 5 mA at maximal input voltageand frequency...

Страница 3: ...breaker and only then turn on theinput AC voltagebreaker The charger will start to supply the load connected at the Consumer output Safemode constant voltage e g 105 Vdc the voltagedepends on theLBC model Inside in series with this output is connected an OR ing diode so two or more LBC systems preferably each onewith his own separate battery can be at theConsumer outputs connected in parallel to s...

Страница 4: ...minal blockHDFK 10 HV Z PhoenixContact Mating part Wires max 10 mm2 torque max 2 Nm OUTPUT and BATTERY CONNECTOR X2 PINOUT SIGNAL NAME PIN TYPE RECOMMENDED WIRES V MAX I MAX CONSUMER Output Power DC Min 16 25 mm2 Max 50 mm2 137 5 VDC 73 110 A BATTERY Output Power DC Min 16 25 mm2 Max 50 mm2 COMMON Output Power DC_return Min 16 25 mm2 Max 50 mm2 Connector type 3 pin terminal block HDFK 50 Z UW50 S ...

Страница 5: ...ull high to limit Address 1 X2 Pin 3 Floating 110 V 138 V FA 14 Floating relay contact normally open closed when in fault condition 0 4A 138Vdc FB 15 Connector type Combicon MSTB2 5 15 GF 1776825 male Phoenix Contact Mating part Combicon MSTB2 5 15 STF 1786967 or FKCN2 5 15 STF 1733084 female Phoenix Contact For models with Suffix S505G or higher Do not connect Second option address setting on req...

Страница 6: ...6 OPERATION MANUAL tech support psbel com MECHANICAL DIMENSIONS Figure3 Front view Weight 23 5 kg LBC8000 29 7 kg LBC12000 ...

Страница 7: ...LBC Series 7 Asia Pacific 86 755 298 85888 Europe Middle East 353 61 225 977 North America 1 408 785 5200 2020 Bel Power Solutions Protection BCM 00432_AJ Figure4 Side and topview ...

Отзывы: