OPERATION MANUAL
MODELS:
LBC8000-1110SxxxG
LBC12000-1110SxxxG
AC INPUT:
3 PHASE
VOLTAGE: 230-277 / 400-480 Vac 3W + PE
CURRENT: 14-9 A (LBC8000)
CURRENT: 21-14 A (LBC12000)
FREQUENCY: 50 / 60 Hz
DC OUTPUT:
VOLTAGE: adjustable 80
–
137.5 Vdc
CURRENT: max. 73 A (8000 W @ 110 V)
CURRENT: max. 110 A (12000 W @ 110 V)
SAFETY APPROVALS
▪
CE Mark
▪
China RoHS
CAUTION
These component level power supplies are intended exclusively for installation within other equipment by an industrial assemb ly operation or by
professional installers. These are Class 1 power supplies; the unit must be properly connected to earth ground in end use. A component power supply
should be installed in end-use equipment according to the requirements of the safety standard used for that equipment. This power supply is not designed
to be operated outside of an enclosure which provides a means of mechanical, electrical, and fire protection.
PROTECTIVE EARTHING
The Power Supply must be properly grounded to mains protective earth termination at end use.
ENVIRONMENTAL CONDITIONS:
TRANSPORTATION & STORAGE: Ambient Temperature Range -40 °C to +85 °C
Relative Humidity Range: 5% to 95% RH Non-Condensing
Altitude: to 12192 m (40 000 feet) ASL
OPERATION: Ambient Temp. Range -25°C to +55°C (at 100% load), to +70°C (at 75% load)
Relative Humidity Range: 10% to 90% RH Non-Condensing
Altitude (ASL): to 2500 m full power, to 3048 m (10 000 feet) derating 90% of full power
INSTALLATION REQUIREMENTS
Recommended power wires dimensions you can find in charts below. The mate parts of connectors are also described below. For t he air inlet and outlet
there is required to maintain a minimum open space 10 cm. For chassis fastening you will need 6x screws M8. The preferred mounting position is vertical,
with connectors on top. The input shall be fused by: Breaker ABB, S203MT, C16, or similar. The output Battery must be protected by following fusing:
Breaker ABB, S802S-UCB125 (125A, char. B), or similar.
WARNING
1.
The equipment is for business use (Class A). In a domestic environment this product may cause radio interference in which case the user may be
required to take adequate measures.
2.
The AC Leakage current exceeds 3.5 mA at maximal input voltage and frequency (3 x 528 VAC / 63 Hz). It is necessary to take appropriate measures
(additional fixed grounding of the chassis).
3.
Do not touch the Output connector X2 during the operation . There is a hazard voltage present, up to 138 Vdc.
4.
Caution, this is a heavy weight unit, 24-30 kg.
SAFETY INSTRUCTIONS
Switch off the input power and disconnect battery (X2) together with connector X3, X1 and wait min. 2 minutes before doing any maintenance on the unit!
SERVICING
In case of failure, the unit must be returned to the Bel Power Solutions Authorized Service Center. There are no user serviceable parts inside, except of the
fan replacement. In case of failure of the fan this can be replaced without whole chassis opening. The procedure is described below.
CORROSION PROTECTION
The unit outside is protected by painting with Soprano 1
–
Art. 095 000298-000. Inside all PC boards are protected by lacquering with Humiseal 1B73.
LIMITED WARRANTY
Bel Power Solutions warrants each power supply of its manufacture for a period of two years from the date of original shipment. This warranty applies to
defects in materials and workmanship that result in non-performance to published specifications. The product(s) must be returned to a Bel Power Solutions
Authorized Service Center for repair with a Bel Power Solutions pre-assigned RMA number.
Bel Power Solutions assumes no liabilities for consequential damages of any kind through the use or misuse of its products by any user. No other obligations
are expressed or implied. Please note that the specifications, terms, and conditions stated are subject to change without notice.