Installation and operating manual
EN
34
METPOINT
®
SF53
6.4.1. Modbus settings (2001 ... 2005)
Modbus
register
Register
address
Byte
Data type
Description
Default
Read/
write
Unit/comment
2001
2000
2
UInt16
Modbus ID
1
R/W
Modbus ID 1…247
2002
2001
2
UInt16
Baud rate
4
R/W
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38400
2003
2002
2
UInt16
Parity
1
R/W
0 = none
1 = even
2 = odd
2004
2003
2
UInt16
Number of
stop bits
R/W
0 = 1 stop bits
1 = 2 stop bits
2005
2004
2
UInt16
Word order
0xABCD
R/W
0xABCD = big endian
0xCDAB = middle endian
6.4.2. Values register (1001 …1500)
Modbus
register
Register
address
Byte
Data type
Description
Default
Read/
write
1101
1100
4
Float
Flow in m³/h
R
1109
1108
4
Float
Flow in Nm³/h
R
1117
1116
4
Float
Flow in m³/min
R
1125
1124
4
Float
Flow in Nm³/min
R
1133
1132
4
Float
Flow in ltr/h
R
1141
1140
4
Float
Flow in Nltr/h
R
1149
1148
4
Float
Flow in ltr/min
R
1157
1156
4
Float
Flow in Nltr/min
R
1165
1164
4
Float
Flow in ltr/s
R
1173
1172
4
Float
Flow in Nltr/s
R
1181
1180
4
Float
Flow in cfm
R
1189
1188
4
Float
Flow in Ncfm
R
1197
1196
4
Float
Flow in kg/h
R
1205
1204
4
Float
Flow in kg/min
R
1213
1212
4
Float
Flow in kg/s
R
1221
1220
4
Float
Flow in kW
R
1269
1268
4
UInt32
Consumption m³ before decimal point
x
R
1275
1274
4
UInt32
Consumption Nm³ before decimal point x
R
1281
1280
4
UInt32
Consumption ltr before decimal point
x
R
1287
1286
4
UInt32
Consumption Nltr before decimal point x
R
1293
1292
4
UInt32
Consumption cf before decimal point
x
R
1299
1298
4
UInt32
Consumption Ncf before decimal point x
R
1305
1304
4
UInt32
Consumption kg before decimal point
x
R
1311
1310
4
UInt32
Consumption kWh before decimal
point
x
R
1347
1346
4
Float
Velocity m/s
1355
1354
4
Float
Velocity Nm/s
1363
1362
4
Float
Velocity Ft/min
1371
1370
4
Float
Velocity NFt/min
1419
1418
4
Float
GasTemp °C
1427
1426
4
Float
GasTemp °F