10
Heatless Desiccant Dryers
|
Instruction Manual
Technical Data
Section 3:
Technical Data
Environmental Conditions
All dryers are designed to be safe under the following conditions:
• Indoor use
• Altitude up to 6560 ft.
• Ambient temperature 41°F (5°C ) to 122°F (50°C)
• Mains supply voltage fluctuations not to /- 10% of nominal
For operation extended from the above conditions, please contact the manufacturer.
Rated Conditions
Measurement
Performance
Inlet pressure
100 psig
7 barg
Inlet temperature
95°F
35°C
Relative humidity of air at inlet
95%
Pressure dewpoint, standard version
-40°F
-40°C
Specified Limitation for Operation
Measurement
Performance
Maximum inlet air pressure
188.5 psig
13 barg
Minimum inlet air pressure
58 psig
4 barg
Maximum ambient air temperature
122°F
50°C
Minimum ambient air temperature
41°F
5°C
Pressure dewpoint*
-4°F to -100°F
-20°C to -74°C
Electrical supply voltage
115 - 240 VAC 50-60 Hz or 24 VDC
Excessive vibrations from external sources may cause failure
of this product.
* Pressure dewpoint dependant upon dryer sizing (see page 12). High performance cartridges required for -100°F (-74°C) operation.