EN
Installation and operating manual
BEKOMAT
®
3/6 CO Ex, 3/6 E Ex
17
BEKOMAT
®
3 CO Ex / 3 E Ex - condensate discharge rate > 360 l/h
1
3
4
2
5
137 (143) mm*
*Mindesteinbauhöhe (mit Bodenhalter)
1
Venting line (Ø ≥ ¾")
Permanently installed pipe
2
Manual drain (Ø ≥ ¼”) (recommended)
Permanently installed pipe
3
Condensate discharge of solenoid valve
(Ø ≥
½”)
Permanently installed pipe at a
continuous gradient (≥ 1°)
4
Condensate discharge of manual drain
(Ø ≥ ¼")
Permanently installed pipe at a continuous
gradient (≥ 1°)
5
Lower condensate inlet (Ø ≥ ¾”)
Permanently installed pipe at a continuous
gradient (≥ 1°)
We recommend installing a floor bracket.
BEKOMAT
®
6 CO Ex / 6 E Ex - condensate discharge rate > 360 l/h
1
3
4
2
163 (169) mm*
*Mindesteinbauhöhe (mit Bodenhalter)
5
1
Venting line (Ø ≥ ¾”)
Permanently installed pipe
2
Manual drain (Ø ≥ ½”) (recommended)
Permanently installed pipe
3
Condensate discharge of solenoid valve
(Ø ≥
½”)
Permanently installed pipe at a
continuous gradient (≥ 1°)
4
Condensate discharge of manual drain
(Ø ≥ ½”)
Permanently installed pipe at a continuous
gradient (≥ 1°)
5
Lower condensate inlet (Ø ≥ 1”)
Permanently installed pipe at a continuous
gradient (≥ 1°)
We recommend installing a floor bracket.