5.  INSTALLATION

5.1 Location
The 

BA444DF-F 

FOUNDATION™ 

fieldbus

indicator  is  housed  in  a  robust  IP66  glass
reinforced polyester (GRP) enclosure incorporating
an  armoured  glass  window  and  stainless  steel
fittings.  It is suitable for exterior mounting  in most
industrial  environments,  including  offshore  and
wastewater treatment installations.  Please consult
BEKA associates if high vibration is anticipated.

The  BA444DF-F  enclosure  is  surface  mounting.
Accessory  kits  described  in  sections  8.3  of  this
manual enable the instrument to  be  mounted  onto
a vertical or horizontal pipe.

The field terminals and the two mounting holes are
located  in  a  separate  compartment  with  a  sealed
cover  allowing  the  instrument  to  be  installed
without exposing the display assembly.

The BA444DF-F earth terminal is connected to the
carbon  loaded  GRP  enclosure.  If  this  enclosure  is
not  bolted  to  a  post  or  structure  connected  to  the
plant potential equalising network, the instrument’s
earth  terminal  should  be  connected  to  the
potential  equalising  network  as  recommenced  in
EN 60079-14.

The  BA444DF-F  enclosure  is  supplied  with  a
bonding  plate  to  ensure  electrical  continuity
between the three conduit / cable entries.

5.2 Installation Procedure
Fig  2  illustrates  the  instrument  installation
procedure.

a.

Remove  the  instrument  terminal  cover  by
unscrewing the two captive 'A' screws.

b.

Mount  the  instrument  on  a  flat  surface  and
secure  with  two  M6  screws  through  the  'B'
holes.  Alternatively use one of the mounting
kits described in section 8.3

c.

Remove  the  temporary  dust  seals  from  the
three  cable  entries  and  install  the  required
glands, conduit fittings or blanking plugs.
Note:    The  temporary  dust  seals  fitted  for
transit do not maintain the IP66 protection of
the BA444DF-F enclosure.
Cable glands, conduit fittings, blanking  plugs
and  cables  must  be  suitable  for  continuous
use  at  the  maximum  operating  temperature
of the instrument.

d.

Connect  the  field  wiring  to  the  terminals  as
shown in Fig 3.

e.  Replace  the  instrument  terminal  cover  and

evenly tighten the two 'A' screws.

Fig 2   BA444DF-F installation procedure

5.3  EMC
The BA444DF-F complies with the requirements of
the  European  EMC  Directive  2004/108/EC.    For
specified  immunity,  all  wiring  should  be  in
screened twisted pairs with the screens earthed at
one point in the safe area.

Fig 3  Dimensions and terminal connections

Содержание FOUNDATION BA444DF-F

Страница 1: ...Issue 3 23 rd June 2011 BA444DF F FOUNDATION fieldbus Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 3...

Страница 2: ...nter address display parameters 6 3 6 Enable selected input 6 3 7 Enter Device Address 6 3 8 Enter Variable Identity 6 3 9 Decimal point position 6 3 10 Configuration of bargraph 6 3 11 Scale numeric...

Страница 3: ...n alternative version of the fieldbus display order code BA444DF P for use on PROFIBUS PA networks 1 1 Documentation This instruction manual describes ATEX system design and installation of the BA444D...

Страница 4: ...ed comply with the Fieldbus Intrinsically Safe Concept FISCO defined in IEC 60079 Part 27 and also have separate entity parameters as shown below FISCO Entity Ui 17 5V dc 22 0V dc Ii 380mA dc 250mA dc...

Страница 5: ...any intrinsically safe segment providing The device powering the fieldbus segment is ATEX certified and has output parameters equal to or less than Uo 22V dc Io 250mA dc Po 1 2W The segment can provid...

Страница 6: ...F F enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 5 2 Installation Procedure Fig 2 illustrates the instrument installation procedur...

Страница 7: ...nditioned as a fieldbus listener see section 6 3 13 to change it to a fieldbus node 6 2 1 Reset the indicator to node factory defaults rESEt The BA444DF F may be reset to the factory defaults that are...

Страница 8: ...the P button causes the BA444DF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Страница 9: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 6 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Страница 10: ...10...

Страница 11: ...isplayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be sele...

Страница 12: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Страница 13: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Страница 14: ...normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BE...

Страница 15: ...After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA...

Страница 16: ...e atmosphere in the form of a cloud of combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is not...

Страница 17: ...sion 1 or 2 Class I Group A B Group C Group D Class II Group E F G Class III Zone 0 1 or 2 Class 1 Group IIC Group IIB Group IIA The FM and cFM entity parameters are identical to the ATEX parameters a...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...24...

Страница 25: ...fety parameters and installation requirements The ATEX system design requirements described in section 4 of this manual may therefore be used for IECEx installations in gas atmospheres but the local c...

Страница 26: ...ay be downloaded from www beka co uk www iecex com or requested from the BEKA sales office A3 3 Versions of the BA444DF F All versions of the BA444DF F fieldbus indicator have IECEx certification This...

Отзывы: