5.4.7 Restart
This function determines what happens at the
end of each batch. There are three options:
Normal:
The display screen shows the
volume that has been
dispensed. Before another
batch can be started the Reset
push-button must be operated.
The screen will then display
‘Ready’.
Quick:
The display screen shows the
volume that has been
dispensed. Operating the Start
pushbutton will reset the batch
controller and start another
batch.
Auto restart: The display screen shows the
volume that has been
dispensed. After a configurable
restart delay (See 5.5.19) the
batch controller automatically
resets and starts another batch.
The number of batch cycles to
be performed is defined by the
Batch Cycle function, which is
contained in the Batch Setting
menu. See 5.5.18
Normal
Quick
Auto
Set Batch Restart
Highlight the required option and press E to
enter the selection.
5.4.8 Output 2
Output 2 is a single pole relay contact that is
connected to terminals A3 and A4. It may be
configured to output any one of six different
signals, or may be unused.
Unused
Control 2
Control 3
Flow alarm
Reset status
Batch status
Pulse Output
Set O/P 2 Function
Highlight the required option and press E to
enter the selection.
Note:
Two or more of the outputs may be
configured to output the same function.
5.4.9 Output 3
As Output 2 except terminals are A5 and A6.
5.4.10 Optional outputs 4, 5 and 6
Only available when factory fitted option is
installed in the BA654D batch controller.
Configuration is the same as for Output 2,
except terminal numbers are:
Output
Terminal numbers
4
A7 (+) & A8
5
A9 (+) & A10
6
A11 (+) & A12
and outputs are single pole solid state.
See 3.4.
5.4.11 Pulse Output
Any of the batch controller outputs may be
configured as a pulse output. The number of
output pulses is proportional to the total
volume dispensed by the batch controller.
This Pulse Output function enables the pulse
output frequency to be reduced by one of five
dividing factors between 10 and 100,000.
Display / 1
Display / 10
Display / 100
Display / 1000
Display / 10000
Display / 100000
Set Output Rate
Highlight the required option and press E to
enter the selection.
Note:
Maximum output frequency is 4 Hz.
5.4.12 Clear Grand Total
The Grand Total is a record of the total
quantity of product dispensed since the Grand
Total was last reset to zero. It must be zeroed
every time the batch controller scaling is
changed
The Grand Total can be viewed in the
Information section of the System Menu – see
section 5.2 and Appendix 2.
CAUTION
After zeroing, the old grand total
can not be recovered
To prevent the Grand Total being accidentally
zeroed, the clear instruction has to be
confirmed before it will be executed.
Clear G Total
Cancel
Clear Grand Total
Содержание BA654D
Страница 1: ...Issue 4 1st December 2010 BA654D Field mounting Batch Controller Issue 4 ...
Страница 9: ...9 Fig 5 Dimensions and terminal connections ...
Страница 12: ...12 Fig 6 System Settings ...
Страница 17: ...17 BLANK PAGE ...
Страница 18: ...18 Fig 9 Batch Settings ...
Страница 23: ...23 BLANK PAGE ...
Страница 24: ...24 Fig 11 Rate Settings ...
Страница 32: ...32 ...
Страница 33: ...33 ...
Страница 34: ...34 Appendix 2 Information menu ...