22

5.5.21 Control output 1 (optional):   

op1

Control output 1 is an optional factory fitted,
galvanically isolated solid state switch contact which
can be configured to turn

on

and

off

when the Timer

enters specified states. When control output 1 is

on

the '1' annunciator on the Timer display is activated.

The function contains four sub-functions,

EnbL

,

op1 on

,

op1 oFF

and

op1 dELA

. To gain access to the

sub-menu select

op1

in the configuration menu and

press

(

which will show the

EnbL

prompt from

which the other sub-functions can be accessed
using the 

&

 or 

*

 button.

Control output 1 may be configured to turn

on

when

the Timer enters a selected Timer state and to turn

off

when the Timer enters another specified Timer

state.

e.g. if

run

is selected in the

op1 on

sub-

function and

done

is selected the

op1 off

function.

Control output 1 will turn

on

when the Timer enters

the

run

state and will stay

on

until the Timer enters

the

done

state.

Alternatively, the control output

phase may be reversed by selecting the

n

states

such as 

n re5et

.   

If control output 1 is required to be

on

in only one

Timer state, this can be achieved with the following
configuration.

op1 on

state required     e.g.  

run

op1 off

n state required  e.g. 

n run

 

In this example when the Timer enters the

run

state

control output 1 turns

on

. When the Timer moves

from the

run

to any other state, control output 1

turns 

off

.

The Timer configuration example in section 6.2. of
this manual illustrate the use of the control outputs.
Further examples can be found in Application Guide
AG374 which is available on the BEKA website. 

5.5.22 Control output 1 enable:   

EnbL

This function allows control output 1 to be enabled
or disabled without altering any other control output
parameters. To check or change the function select

EnbL

from the control output 1 sub-menu and press

(

to reveal if control output 1 is

on

or

oFF

. The

setting can be changed by pressing the

&

or

*

button followed by the

)

button to return to the

control output 1 output sub-menu.

5.5.23 Control output 1 

on

 at :  

op1  on

Control output 1 may be configured to turn

on

when

the Timer enters in any one of the five Timer states.
Alternatively, the control output 1 phase may be
reversed, by selecting an

n

state which will cause

the control output to turn

on

when the Timer enters

any other than the specified Timer state.

Timer

states are shown in Fig 8.   

To define when control output 1 turns

on

select

op1 on

from the sub-menu and press

(

to show the

existing setting. Pressing the

&

or

*

button will

scroll through the options:

Display

      Control output 1 turns 

on

  

when Timer enters selected state

re5et

Reset state 

run

Running state

pau5ed

Paused state

delay

Restart delay state

done

Complete state

      Control output 1 turns

 on

  

                               when Timer enters any other than 
                                             the selected state 

n re5et

Reset state 

n run

Running state

n pau5ed

Paused state

n delay

Restart delay state

n done

Complete

 

state

When the required setting has been selected press

)

to enter the selection and return to the sub-

menu.

Содержание BA577E

Страница 1: ...Issue 4 3rd July 2018 BA577E One input General purpose Timer or Clock Issue 4...

Страница 2: ...epeat timing cycle CYCLE5 5 5 12 Cycle function enable EnbL 5 5 13 Cycle count cycl cnt 5 5 14 Restart delay r5t dela 5 5 15 Adjusting the set time 5Et t and restart delay r5t dela from the display mo...

Страница 3: ...8 4 8 Enable Control output 1 EnbL 8 4 9 On and off times oP 1 on 1 oP 1 off 1 oP 1 on 2 oP 1 off 2 8 4 10 Control output 2 Optional oP2 8 4 11 Enable control output 2 EnbL 8 4 12 On and off times oP2...

Страница 4: ...s the basic circuit that is used for all BA577E Timer installations Clock installations are the same except that the input terminals 5 6 are not used For simplicity the optional control outputs are de...

Страница 5: ...e circuit to prevent false triggering of the instrument Three levels of debounce protection are available See section 5 5 6 2 2 5 Voltage pulse input Two voltage pulse input ranges are independently s...

Страница 6: ...ecommended panel cut out dimensions To achieve an IP66 seal between the instrument enclosure and the instrument panel the smaller tolerance aperture must be used Although the front of the BA577E has I...

Страница 7: ...g clamps 3 4 Scale card The BA577E s units of measurement are shown on a printed scale card in a window at the right hand side of the display The scale card is mounted on a flexible strip that is inse...

Страница 8: ...lay through which a scale card showing the units of time such as hours can be seen New instruments are fitted with a scale card showing the units of measurement specified when the instrument was order...

Страница 9: ...plished via the front panel push buttons or by a remote contact A grand total time is maintained which can be viewed by operating the front panel push buttons It may be reset to zero from within the c...

Страница 10: ...5 Shows in succession firmware version number instrument function elap5e and any output accessories that are fitted A Dual Control Outputs Access to configuration menu 5 3 Displays when configured as...

Страница 11: ...t the end of the delay time automatically returns to Running Complete Entered automatically from Running when there are no more timing cycles to perform When the CYCLE5 function is enabled the timing...

Страница 12: ...he instrument using the or push button to adjust the flashing digit and the push button to transfer control to the next digit If the correct code has been entered pressing will cause the first paramet...

Страница 13: ...ContACt Switch contact Energise input by linking terminals 3 4 See section 5 5 5 dEbounCE Defines the level of debounce applied to the input to prevent false functioning dEFAuLt HEAVY LiGHt See sectio...

Страница 14: ...display mode to 5Et t and r5t dela See section 5 5 15 Display Summary of function uP or dn Direction of count Defines whether the Timer times down from 5Et t to zero or times up from zero to the set...

Страница 15: ...as control output 1 See section 5 5 26 Display Summary of function CLr Gtot Reset grand total to zero This function resets the grand total which represents the total Timer run time from within the con...

Страница 16: ...s twice to return to the configuration menu or repeatedly press the or button until the required type of input is displayed and then press twice to return to the configuration menu One of following si...

Страница 17: ...at start of each period 02 11 Current Number of cycles cycle requested not shown number when cycle is continuously repeated LabEL Exactly the same as 5td but timer status i e CYCLE or dELAY is shown p...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...o the next digit When set as required enter the selection and return to the cycl cnt prompt in the sub menu by operating the button 5 5 14 Restart delay r5t dela This sub function defines the time del...

Страница 21: ...diately Continue When power is restored the Timer will continue from where it stopped without any manual intervention To check or change the function select P fail from the configuration menu and pres...

Страница 22: ...ation example in section 6 2 of this manual illustrate the use of the control outputs Further examples can be found in Application Guide AG374 which is available on the BEKA website 5 5 22 Control out...

Страница 23: ...select op1 dELA from the control output 1 sub menu and press which will reveal the existing delay time with one digit flashing The flashing digit can be adjusted using the or button and the button to...

Страница 24: ...trol to the second digit which should be set to u When 5urE has been entered pressing the button will reset all the configuration functions and return the instrument to the display mode Note r5Et dEF...

Страница 25: ...topped when the start button is operated Fig 11 Control of a solenioid valve The required instrument configuration for this example are shown below Function Display Setting Access code CodE 0000 Funct...

Страница 26: ...configuration menu Incorrect security code That the correct security code is being used Contact BEKA if code is lost 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENAN...

Страница 27: ...regularly checked Inspection frequency should be chosen to suit the environmental conditions 7 5 Guarantee Instruments which fail within the guarantee period should be returned to BEKA associates or o...

Страница 28: ...ment s permanent memory Following initialisation the instrument will display a flashing display which is a request for the local time to be entered The clock will not start to function until a display...

Страница 29: ...out this manual push buttons are shown as and and legends displayed by the Clock are shown in a seven segment font as they appear on the instrument e g di5PLAY and CodE Access to the configuration men...

Страница 30: ...30...

Страница 31: ...ntrol output 1 Optional Control output 1 can turn on output closed and off output open twice in each twenty four hour period This function contains five sub function EnbL Enables output 1 and defines...

Страница 32: ...time is entered the Clock will display a flashing 00 00 00 or 00 00 for 24 hour formats or A12 00 00 or A12 00 for 12 hour formats To adjust the clock set time select 5Et from the configuration menu a...

Страница 33: ...tered return to the configuration menu by pressing the button twice 8 4 10 Control output 2 Optional oP2 Control output 2 is an optional factory fitted output which can be configured to turn on output...

Страница 34: ...m the display mode may be protected by a four digit alphanumeric security code which must be entered to gain access Default security code 0000 allows unrestricted access With ACCd displayed press to e...

Страница 35: ...ill then change the instrument to a Clock and return the display to FunCtion in the configuration menu Step 3 Select display format Using the or button select di5PLAY in the configuration menu and pre...

Страница 36: ...sed access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the security code...

Страница 37: ...ANCE If a BA577E fails after it has been functioning correctly as a Clock the following table may help to identify the cause of the failure Symptom Cause Check No display No power supply That there is...

Страница 38: ...8 10 6 Customer comments BEKA is always pleased to receive comments from customers about our products and services All communications are acknowledged and whenever possible suggestions are implemented...

Отзывы: